Installation Considerations
Three methods are available to install the Wall Connector. The location of the conduit determines
which installation method to follow. If the conduit runs along the floor or low on the wall, use the
bottom entry configuration. If the conduit comes from inside the wall, use the rear entry
configuration. If the available conduit comes from the ceiling, use the top entry installation.
Note: Throughout the manual, “conduit” is used as the standard term for the protective tubing
that houses the service wiring. In regions where conduit is not used (Europe for example), a cable
comprised of service wiring enclosed in a protective jacket may be substituted for conduit if
allowed by local regulations.
Here are some additional guidelines:
•
Conduit openings are sized for 1" (25 mm) conduit.
•
Conduit needs to be metal and flame retardant.
•
Use an appropriate circuit breaker.
•
To keep the housing weatherproof, use cable glands.
•
Use a UL approved conduit hub, Eaton HUB3 or equivalent is recommended.
Bottom or Rear Entry
Planning Your Installation
Planning Your Installation
11