4. PARTS DESCRIPTION
1
2
3
4
5
6
7
To avoid damage to instrument, never use a sharp
object to press keys.
1. Measured value (PV) display [Green]
* Displays PV or various
parameter symbols
3. Indication lamps
*Control output lamps (OUT,OFF)
[Green] OUT:Light when output is turned on.
[Red]OFF:Light when output is turned off.
4. (Set key)
Used for parameter
calling up and set
value registration
7. (Up key)
Decrease numbers
6. (Down key)
Decrease numbers
CAUTION
5. Shift &Assistant key
2. Set value(PV)display [Red]
* Displays SV or various
parameter set values
SET
*Alarm output lamps (AL1,AL2)
[Red]
AL1: Lights when alarm 1 output
is turned on.
Al2: Lights when alarm 2 output
is turned on.
*Autotuning (AT) [Green]
Flashes when autotuning is
activated.
5. SETTING
5.1 Calling up procedure of each mode
*1. Input type and input range display
This instrument immediately confirms input type and range following power on.
Example: For a controlleer with the K thermocouple input type and range from 0 to 1300
C
.
1. Input type display
:Indicates input type (See table **A)
**A: Input type table(see "14.0 Input range table")
Power on
Power on
Input type display
Input range display
Display changes automatically
(Display for
approx.5 sec)
PV/SV display mode
(Normal display)
The instrument returns to the PV/SV
display mode status if key operation
is not performed for more than 1 minute.
SV setting mode
Parameter Setting Mode
(PID level)
Press the
SET
key
Press the
SET
key
*
1
Initialization Mode
(Input level)
Press the
SET
key
for 3 sec .
Press the
SET
key
for 3 sec .
Press the
SET
key
for 3 sec .
SV
PV
: Input range high
Display
Display
Input
Input
K
Pt100
J
Cu50
E
S
DC0-5V or
DC0-10V
DC2-10V
N
DC1-5V or
T
Thermocouple
Standard analog signal(Voltage and current)
Resistance thermometer
B
W5Re/W26/Re
R
DC0-20mA
DC4-20mA
Press the key while
pressing the
SET
key for
3 secretary.
5.4 PID level (Parameter List)
Press the "
SET
"key for 3 seconds to PID level
The following parameter symbols are displayed one by one every time the SET key is pressed.
After the value be registered ,you can press "SET"key for 3 seconds to return the instrument
to the PV/SV display mode.
Symbol
Name
Setting range
Description
#1: Factory set value
#1
Alarm2 set value
AL2
for low alarm
Alarm1set value
AL1
for high alarm
Deviation orProcess alarm,
-1999 to 9999
Deviation orProcess alarm,
-1999 to 9999
Set the alarm1 set value for high alarm.
Alarm differential gap=HYS,when P 0
Set the alarm2 set value for low alarm.
Alarm differential gap=HYS,when P 0
10
200
PV bias
-1999 to +9999
0 to 9999
Sensor correction is made by adding bias
value to measured value(PV).
0.0
0
Differential gap
for alarm or output
Alarm differential gap=HYS,when P 0(PID action)
Out differential gap=HYS,when P=0 (ON/OFF action)
(4) Set value entry
After finishing the setting, Press
the SET key, All of the set value
digits stop flash and as a result
the instrument return to
PV/SV display mode.
PV
SV
5.2 Setting set value(SV)
Example: Following is an example of set value(SV) to 200 C
(2)Shift of the digit brightly lit
(3) Numeric value change
Press the UP key to set "2".
Pressing the UP key increase
numerals, and pressing the
DOWN key decrease
numerals.
PV
SV
PV
SV
PV
SV
(1)Set to the SV setting mode
In the normal display mode
Press the SET key to enter the
SV setting mode.
The digit which flashing
is settable.
Press the shift key to
shift the digit which lights
brightly up to the hundreds
dights
Caution
*Even if the displayed value is changed, it is not registered. To register it , press the SET key.
The setting procedures are the same as those of example (2) to (4) in the above "Setting set value (SV)". Press the SET key after the
setting end shifts to the next parameter. When no parameter setting is required, return the instrument to the PV/SV display mode.
5.3 Setting parameters other than set value (SV)
Continued on the next page
TS80B-E1