24
V. INSTALLATION PROCEDURE
5.1 Introduction
WARNING!!!
•
Do not apply electrical power to the UPS equipment before the arrival of authorized service personnel.
•
The UPS equipment should be installed by a qualified service personnel.
•
The connection of the batteries and the maintenance should be done by the qualified service personnel.
•
Do not make short- circuit to the batteries poles. Because of the high short-circuit current, it there is the
danger of electrical shock or burn.
•
Keep the batteries away from fire. If there is leakage of electrolyte from a battery or if there is damage in a
battery, put it into a container which is resistant to sulfuric acid. And discard it according to the local
regulations.
•
In case of a spatter of acid from a battery, wash the injured area with water and immediately contact a
doctor.
•
Batteries should always be discarded according to the local regulations.
•
Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and
all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the establishments have
their own specialties and needs. So in this part the installation procedure is not being explain step by step.
Instead general procedure and the applications are explained for the technical personnel.
5.2
Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1.
Inspect for damage that may have occurred during the shipment If any damage is noted, call the shipper
immediately and retain the shipping carton and the UPS.
2.
Carefully open the carton and take the UPS out.
3.
Retain the carton and packing material for future use.
Unit package contents :
•
User Manual
•
Guarantee Certificate
•
Battery cabinet and/or shelf
•
Battery Circuit Breaker (Optional)
5.3 Equipment Positioning
ATTENTION:
Units are designed to operate on the concrete floor.
1.
The equipment’s installation place must be an easy serving place.
2.
Install the UPS in a protected area with adequate air flow and free of excessive dust.
3.
You must therefore allow for a minimum gap of 1000 mm behind the unit to allow adequate air flow (See
Figure 5.1)
4.
Select a suitable place (temperature is between 0
°
C and 40
°
C) and the relative humidity (%90 max)
5.
It is recommended to air-conditioned the room (24
°
C)
6.
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote
figures for an operating temperature of 20
°
C. On a normal installation the battery temperature
is maintained between 15
°
C and 25
°
C. Keep batteries away from main heat sources or main air inlets etc.
7.
In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration system.
8.
Keep out of your equipment from the explosive and flammable items.
9.
Avoid direct sunlight, rain, and high humidity.
WARNING!!!
Check the capacity of the forklift if it is available for lifting.
DO NOT MOVE THE BATTERY CABINET WHILE THE BATTERIES ARE INSTALLED.
Содержание T-3250
Страница 1: ...USER MANUAL T 300P SERIES T 3250 T 3300 250 300 kVA 3 Phase Input 3 Phase Output 12 Pulse Rectifier...
Страница 2: ......
Страница 31: ...27 Figure 5 2 250 300 kVA UPS Power Connections SPLIT BY PASS CONNECTIONS NORMAL CONNECTIONS...
Страница 33: ...29 Figure 5 3 a 250 kVA UPS Battery Group Connections KGK KGK BATTERY GROUP 1 BATTERY GROUP 2 UPS UPS...
Страница 34: ...30 optional Figure 5 3 b 300 kVA UPS Battery Group Connections KGK KGK BATTERY GROUP 1 BATTERY GROUP 2 UPS...
Страница 41: ...37...
Страница 42: ...AGKK6142 02 2010...