21
IV. OPERATING INSTRUCTIONS
NOTE:
In the surroundings of 30 meters radio appliances and radio broadcasting may be disturbed.
The surrounding must be observed against radio interferrences. In case the manufacturer has to support
suitable modifications.
4.1 Introduction
The Operating instructions will be considered in two parts:
1.
The operating instructions for a single UPS (ONLINE OPERATION)
2.
The operating instructions for two UPS’s which are connected in parallel.
4.1 OPERATING INSTRUCTIONS FOR A SINGLE UPS UNIT. (ONLINE OPERATION)
4.2.1 Procedure For Switching The UPS To Power The Load From a Power-Off Condition :
By applying this procedure UPS returns to normal operation, when it is completely off.
ATTENTION !!!
The following action will apply power to the load equipment.
1)
Make sure that all the switches and fuses (S1, S2, S3, S4 and S5) are in “OFF” position and S6 is in
“NORMAL” position.
NOTE THAT S6 SHOULD ALWAYS BE IN “NORMAL” POSITION FOR ONLINE OPERATION
2)
Turn S2 switch (static bypass) into “1” (ON) position.
3)
Turn on S4 (output switch), now the load is connected to bypass supply.
4)
Turn on the S1 switch (rectifier input), into ”1” position. By turning on S1, all lights on the front panel will
be lit for 4 secs (lamp test) and then, the following messages will appear on LCD.
“RECTIFIER START” : Rectifier is operating and static bypass continues to supply the load.
“INVERTER START” : Inverter is operating and static bypass continues to supply the load.
“STATUS NORMAL”
: The UPS is operating normally and the inverter is supplying the load.
ATTENTION : AC output voltage is applied to the load at this step.
5)
Turn on the S5 (The battery circuit breaker) into “1” position or insert the battery fuse. By this way, the
battery group is connected to the UPS.
6)
Once you see the green inverter led on the front panel then the UPS system is now ready for use. You
can start up your PC, printer and other critical loads.
ATTENTION :
For using as a single unit, the UPS must be operated in “ONLINE” mode, and the
Mode Selection can be made as follows:
•
Using the UP-DOWN buttons on the front panel, select “SETTINGS MENU” on LCD
and press “ENTER”. When you see “MODE” display, using “+” and “-“ buttons select
“ONLINE” mode.
•
After selecting ONLINE mode press “ENTER” until the beep sound stops.
•
Turn off S1 and after a few seconds, turn it on again. You will see “INVERTER
START” and than “STATUS NORMAL” messages on the LCD.