13
NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
13
5.3 UPS On/Off operation
Operation
Description
Turn on the UPS
> Turn on the UPS with mains power
l
With mains power connected, UPS works in bypass mode, its output is same
as the input voltage within the input range. If there is no need of output voltage
when mains power connected, you can set up bPS to ‘OFF’. Default bPS is
ON, it means there is bypass output when power on.
l
Press the ON key for more than half a second to start the UPS, then it will start
the inverter.
l
Once started, the UPS will perform a self-test function. When the self-test
finishes, it will turn to online mode.
> Turn on the UPS by battery without mains power
l
When main power is disconnected, press the ON key for more than half a
second to start UPS.
l
The operation of UPS startup process is almost same as above process with
mains power. After the self-test finishes, UPS will work in battery mode.
Turn off the UPS
> Turn off the UPS in Line mode
l
Press the OFF key for more than half a second to turn off the UPS.
l
After UPS shutdown, there is no output. If output is needed, you can set BPS
‘ON’ on LCD setting menu.
> Turn off the UPS in battery mode without mains power
l
Press the OFF key for more than half a second to turn off the UPS.
When UPS shut down, it will do self-test first, until there is no display on the
panel.
UPS self-
test/mute test
operation
l
When UPS is in LINE Mode, press the self-test/mute key for more than 1
second. UPS gets to self-test mode and tests its status. It will exit automatically
after finishing test.
l
When UPS is in BAT Mode, press the self-test/mute key for more than 1
second, the buzzer stops beeping. If you press the self-test/mute key for one
more second, it will restart to beep again.
UPS Setting
l
Enter Setup interface. Press and hold the function setting key
for more
than 2 seconds, then come to Setup interface, press and hold the inquiring key
(
,
) for more than half a second (less than 2 seconds), select the
function setting, choose the setup interface, at the moment, the letters flash.
l
Enter the setup interface. Press and hold the function setting key
for
more than half a second (less than 2 seconds), then come to the setup
interface, at this time, the letters doesn’t flash any more, the numerical value
flash. Press and hold the inquiring key (
,
) for more than half a
second (less than 2 seconds), select the numerical value in accordance with
the function.
l
Confirm the setup interface. After selecting numerical value, press and hold
the function setting
for more than half a second (less than 2 seconds).
Now, the setting function is completed and the numerical value illuminates
Содержание NEOLINE PRO 1kVAS
Страница 7: ...5 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 2 2 Real panels features 1kVA 2 kVA...
Страница 29: ...27 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 1 1 1 1 UPS UPS UPS UPS UPS UPS UPS 1 2 UPS...
Страница 30: ...28 www tescom ups gr NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL A AC DC...
Страница 33: ...31 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 3kVAS DC72V AC Port RS232 USB EPO...
Страница 35: ...33 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL UPS UPS UPS UPS UPS UPS 8 AC UPS UPS UPS 3 3 1 3kVA UPS UPS...
Страница 43: ...41 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 15 UPS UPS v1 7 40 220V 50Hz 24V 100 5 6 LCD UPS UPS...
Страница 45: ...43 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 17 CUCF CUCF LCD CUCF CUCF 70 UPS UPS UPS UPS LCD OFF UPS...
Страница 49: ...47 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL EEPROM 0 1 2 3 4 5 6 7 8 9 A B E 0 1 2 3 4 5 6 7 2000 LCD...
Страница 51: ...49 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL LCD UPS On 2 UPS UPS UPS UPS UPS 3 UPS UPS UPS UPS UPS AC...