24
OPTIONS / ALARM OPTIONS
Page 1 (Level 3)
>WARNING INTRVL:10 sc
Warning beep interval adjustment in seconds
WARNING LOG:ON/OFF
Left and right warning LOG record ON/OFF
STATUS LOG:ON/OFF
Left and right status log record ON/OFF
……………………………..
Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option
OPTIONS / ALARM OPTIONS
Page 2 (Level 3)
>ALF RESTART: USER/AUTO
During mains restore start USER/AUTO
(R1174/2)
……………………………..
Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option
OPTIONS / ALARM OPTIONS
Page 3 (Level 3)
ENTER - EXIT
ENTER exit to upper menu
……………………………..
Current alarm messages
Up previous page, down next page
Level 3 - Bypass options
VAT transfer ON/OFF
Page1
Gen set bypass ON/OFF
Page1
Gen set synchron ON/OFF
Page1
ENTER - EXIT
Page2
OPTIONS / BYPASS OPTIONS
Page 1 (Level 3)
VAT TRANSFER:ON/OFF
Left and right VAT transfer system ON/OFF
(R1174/3)
>GEN SET BYP:FORBID/FREE
Left and right bypass to generator FORBID/FREE
(R1174/5)
GEN SET SYNC:XTAL/SYNC
Left and right generator synchron XTAL/SYNC
(R1174/6)
……………………………..
Current alarm messages
Up upper line ,down next line ,(+) or (-) options ,ENTER select an option
OPTIONS / BYPASS OPTIONS
Page 2 (Level 3)
ENTER - EXIT
ENTER exit to upper menu
……………………………..
Current alarm messages
Up previous page ,down next page