3.5.2
Test Probe Terminals
The test probe terminals are provided on the EC Motor Control Card to measure the motor RPM or check for a PWM
signal using a multimeter.
Manual or Analog Control Modes:
To measure RPM, set the Address DIP Switches at a value greater than 1. The test probe jacks will output 0-2000
mVDC to represent motor RPM.
Example: 500 mVDC = 500 RPM
To measure demand signal, change the Address DIP Switches to the value of 0.
Note:
Changing the address will not interrupt power to the Control Card.
Network Control Mode:
In the MODBUS® network control mode, the test probe terminals will always output 0-2000 mVDC to represent motor
RPM.
Note:
Address zero should not be used for Networked Control mode as it is reserved for global commands.
Note:
The EC Motor Control Card must be power-cycled for any address changes to take effect.