DPTH High Accuracy Differential Pressure Transmitter-Operation Manual

Edition: A/2

2

Connection

Different models have different electrical connections.

RS485/Modbus communication refer to “DPT series Modbus Communication Manual”. RS485 terminal resistance jumper J8 is

described as follows

:

Terminal resistance 120 Ω

the jumper J8 is at position “on”

Terminal resistance 0 Ω(None)

the jumper J8 is at position “off”

As shown below:

Button

“SET”: Set/Confirm/Save; “SEL”: Bit Select/Decrease/ Zero Reset

press for 5s

; “ADJ”: Adjust/Increase;

See the operation instruction for the button operation.

SET

SEL

ADJ

Installation

● The installation site should be far away from heater, cooler, fan or other humidity and ventilation sources. Figure 1 is bottom

view of the product, for opening the 4 holes on the mounting surface.

● It should to be installed vertically on the wall, with the outlet gland downwards, shown as figure 2. Open the front cover and

screw the base on the mounting surface with 4 mounting screws.

● Feed the cable into the base through the cable gland, finish wiring according to the wiring diagram. Restore the front cover and

finish the pressure connection, pay attention to the difference between high (+) and low (-) pressure ports. Make sure to

completely air-tighten the gland to the base and the cover to the base with the seal rings, thus the housing overall protection

rate could meet up to IP65.

Zero reset & Calibration

According to different environment and sensor’s characteristics, for long term of using, the sensor’s accuracy maybe drift. The

transmitter should be zero reset after initial power on to meet the specified accuracy, and be zero reset periodically in every 6-12

months’ using. It is recommended to be “zero reset” after the initial 7 days continuous working.

Zero reset: keep the high

+

/low

-

pressure ports unconnected in stable air, or directly connect them, press the button “SEL”

for 5s to perform “zero reset”. It means “remove the zero drift of the transmitter in order to improve the accuracy”. It

isrecommended that this operation could be done periodically.

RS485

9600,8,N,1

Slave Add.= 1

B

A

V

POWER   SUPPLY

24VDC

A

POWER   SUPPLY

24VDC/AC

V+     GND     OUT

V

oltage Output Model

Current Output

RS485 Model

POWER   SUPPLY

24VDC/AC

V+      OUT

V+      GND      B       A

   120

J8

O

N

1

   120

J8

O

N

1

Terminal resistance

120

 Ω

Terminal resistance

None Default

Figure 1

Figure 2