Service schedule 

It is done by authorized personnel and includes the following activities:  

1. Inspection for visible physical damage  

 

 

- monthly  

2. Testing in real conditions  

 

 

 

 

- monthly  

3.* Preventive cleaning of the optic chamber    

- every 6 months  

*The fire detector is removed from the base. The body cover (fig.1,pos.6) is removed by rotating to 
rest anticlockwise. The optic chamber cover (fig.1,pos.7) and the screen (fig.1,pos.8) are removed. 
For  the optic chamber  cover and the  screen it  is permitted washing liquid  to  be used. Then they 

should be rinsed out and dried. The optic chamber is dusted with a small brush.  
The  optic  chamber  is  compulsory  dusted  when  the  fire  detector  enters  Contaminated  chamber 
Mode. If it is not cleaned in due time it will get contaminated to such an extent that it would not 

allow the proper functioning of the fire detector which will be signaled as Fire Condition.  

Warranty 

FD8030 and 8000R are manufactured by Unipos Ltd.  
The  manufacturer  guarantees  the  normal  operation  of  the  fire  detector  providing  that  the 
requirements set herein have been observed. The manufacturer does not bear warranty liabilities 

for  damages  caused  through  accidental  mechanical  damage,  misuse,  adaptation  or  modification 
after  production.  The  manufacturer  bears  warranty  liabilities  for  damages  in  the  fire  detector 
caused through manufacturer's fault only. 