TSS8030R_R2.2 – October 2018
Page 1
Smoke detector
TSS8030R
Short description
TSS8030R smoke detector is designed for early warning of a fire condition responding to fixed
threshold smoke concentration detected in the protected premises. The smoke sensitivity is factory
preset.
The principle of functioning of the detector is based on infrared rays distraction caused by smoke
particles entering the optic chamber. The fire detector is controlled by a microprocessor, operating
on the basis of improved algorithm for self-compensation of the chamber contamination.
Technical parameters
Supply voltage range
10 to 30 VDC
Maximum supply current
18mA/10VDC
55mA/30VDC
Smoke sensitivity
complies with
EN 54-7:2000+ A1:2002
Time to enter Duty mode after power supply is on
up to 40s
Reset time
2s
Time to enter Duty mode after reset
up to 40s
Protected area
circle with diameter 15 m
Height of mounting
up to 11 m
Operating temperature range
-10 to +55 °C
Operating humidity
resistance
(93 ± 3)% at 40°C
Dimensions
Ø100 mm, h 47mm
Weight
0,100 kg
Cross section of the connecting wire
0.8 to 1.5 mm²
LED indicators
Both LED indicators (pos.3) allow range of visibility 360° and provide information for the status:
-
Duty mode - the LEDs are not lit;
-
Fire condition - the LEDs produce continuous light;
-
Contaminated chamber- the LEDs flash briefly every 1s.