01 Illegal function
The function code received in the query is not an allowable action for the
controller.
02 Illegal data address
The data address received in the query is not an allowable address for the slave.
More specifically, the combination of the reference number and transfer length is
invalid. For a controller with 100 registers, a request with offset 96 and length 4
would succeed, a request with offset 96 and length 5 will generate exception 02.
8.3.2.
Address table
Parameter
FC
PDU
decimal
address
Data size
Data
Number of installed sensors
03
18000
16-bit Integer
Sensor 1-8 description
03,06,16 18100
64 bytes UTF-8
Sensor 1-8, Part 1-3 dimension 03,06,16 18400
64 bytes UTF-8
Sensor 1-8, Part 1-3 max
03,06,16 19200
32-bit Float
Sensor 1-8, Part 1-3 min
03,06,16 19300
32-bit Float
Sensor 1-8, Part 1-3 hysteresis
03,06,16 19400
32-bit Float
Sensor 1-8, Part 1-3 multiplier
03,06,16 19500
32-bit Float
Sensor 1-8, Part 1-3 offset
03,06,16 19600
32-bit Float
Sensor 1-8 ID
03
19700
16 bytes UTF-8
Example: 2860B85F07000094
Sensor 1-8, Part 1-3 value
03
19800
32-bit Float
Sensor 1-8, Part 1-3 row value
03
19900
32-bit Float
Sensor 1-8 alarm status
03
20000
16-bit unsign int normal (0), alarm (1)
Save configuration
03,06
50000
16-bit unsign int unsaved (0), saved (1)
Restart device
03,06
50001
16-bit unsign int cancel (0), restart (1)
Temperature unit
03,06
50002
16-bit unsign int Celsius (0), Fahrenheit (1)
HW error
03,06
50003
16-bit unsign int noErr (0), hwErr (1)
Device ID
03
50100
18 bytes UTF-8
Example:
5c:32:c5:00:ac:52
Hostname
03
50200
16 bytes UTF-8
Device IP
03
50300
16 bytes UTF-8
Example:
192.168.1.2