TCW210-TH-R1.2 - January 2018
Page 18
8.
Protocols and API
8.1.
SNMP
Simple Network Management Protocol (SNMP) is a standard internet protocol for managing
devices on IP networks. In typical uses of SNMP, one or more administrative computers,
called managers, monitor and control devices on LAN. Each controlled device, at all times,
executes a software component called an agent which reports information via SNMP to the
manager.
The TCW210-TH can be configured and monitored through SNMP.
This could be done using every SNMP v.2 compatible program. Parameters that can be changed,
are grouped according to their functions in the tables below. To obtain a valid OID number it is
necessary to replace the “x” symbol with ”1.3.6.1.4.1.38783”.
To save the changes configurationSaved (OID x.2.3.5.0) should be set to "1".
product
OID
Name
Access
Description
Syntax
x.4.1.1.0
name
read-only
Device name
DisplayString
x.4.1.2.0
version
read-only
Firmware version
DisplayString
x.4.1.3.0
date
read-only
Release date
DateAndTime
setup -> network
OID
Name
Access
Description
Syntax
x.4.2.1.1.0
deviceID
read-only
Device ID (default MAC address)
MacAddress
x.4.2.1.2.0
hostName
read-only
Hostname
DisplayString
x.4.2.1.3.0
deviceIP
read-only
Device IP address
IpAddress
setup -> io -> sensorsSetup -> sensor1setup
OID
Name
Access
Description
Syntax
x.4.2.2.1.1.1.0
s1description
read-write
Sensor 1 description
DisplayString
x.4.2.2.1.1.2.1.0
s11MAXInt
read-write
S11 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.1.2.2.0
s11MINInt
read-write
S11 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.1.2.3.0
s11HYSTInt
read-write
S11 hysteresis value x1000 in Integer format
Integer32
x.4.2.2.1.1.3.1.0
s12MAXInt
read-write
S12 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.1.3.2.0
s12MINInt
read-write
S12 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.1.3.3.0
s12HYSTInt
read-write
S12 hysteresis value x1000 in Integer format
Integer32
x.4.2.2.1.1.4.1.0
s13MAXInt
read-write
S13 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.1.4.2.0
S13MINInt
read-write
S13 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.1.4.3.0
s13HYSTInt
read-write
S13 hysteresis value x1000 in Integer format
Integer32
setup -> io -> sensorsSetup -> sensor2setup
OID
Name
Access
Description
Syntax
x.4.2.2.1.2.1.0
s2description
read-write
Sensor2 description
DisplayString
x.4.2.2.1.2.2.1.0
s21MAXInt
read-write
s21 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.2.2.2.0
S21MINInt
read-write
S21 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.2.2.3.0
S21HYSTInt
read-write
S21 hysteresis value x1000 in Integer format
Integer32
x.4.2.2.1.2.3.1.0
S22MAXInt
read-write
S22 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.2.3.2.0
S22MINInt
read-write
S22 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.2.3.3.0
S22HYSTInt
read-write
S22 hysteresis value x1000 in Integer format
Integer32
x.4.2.2.1.2.4.1.0
S23MAXInt
read-write
S23 maximum value x1000 in Integer format
Integer32
x.4.2.2.1.2.4.2.0
S23MINInt
read-write
S23 minimum value x1000 in Integer format
Integer32
x.4.2.2.1.2.4.3.0
S23HYSTInt
read-write
S23 hysteresis value x1000 in Integer format
Integer32