background image

2

/

6

 

 

3.  

PURPOSE

 

 

Explosion protected installation switches, type SKX-SW/1, SKX-SW/2, SKX-SW/6 are use for on and off light circuits up to 16A in 
industrial with potentially explosive atmosphere in Zones 1, 2 accordance with EN 60079-10-1:2009. 

 

4.  

PRODUCT COMPLIANCE

 

 

The product is accordance with the standards EN 60598-1:2008 and related standards. 
The  product  is  in  compliance  with  Regulations  concerning  equipment  and  protective  systems  for  use  in  potentially  explosive 
atmosphere. 
The product complies with the ATEX Directive 94/9 EC and standards: 

-

 

EN 60079-0:2012, 

-

 

EN 60079-1:2007, 

-

 

EN 60079-7:2007. 

The product has been developed,  manufactured and tested according to the existing state of technique accordance with the standards 
EN 9001:2008 and EN ISO / IEC 80079-34:2011. 
The product is in compliance with the LV Directive 2006/95 EC. 
The product is in compliance with the RoHS Directive 2011/65 EU. 
The product is in compliance with EMC Directive 2004/108 EC. 
 
The sing X is placed after the certificate number, it indicates that product is subject to specific conditions. The cable glands was tested 
with  lower  impact  energy  and  lower  extraction  force  accordance  to  EN  60079-0:2012,  therefore  it  has  to  be  installed  in places  with 
lower risk of impact and additional clamping of the cable. 

 

5.  

DEGREE OF PROTECTION AND TECHNICAL DATA

 

 

Certificate: 

EXA 15 ATEX 0006X 

Marking: 

         

0722 

Category and  
explosion protection: 

 

II 2G Ex d e IIC T6 Gb 

Ambient temperature: 

-20ºC ≤ T

≤ +40/50ºC

 

Mechanical protection: 

IP 54  

Resistance to shock: 

IK 08  

Class of protection: 

I (PE - protective earthing) 

Rated isolating voltage U

i

690 V 

Rated thermal current I

th

16 A for -20°C ≤ T

a

 ≤ +40°C 

15 A for -20°C ≤ T

a

 ≤ +50°C 

PE terminal within housing: 

max. 2x4mm

2

 + 2x2,5mm

2

, 3x4mm

2

, 2x6mm

2

 –  

solid, stranded, flexible  

Cable entries: 

2 x M25 entries with 1 x SPU 25 (Ø

V

 7-15mm) and 1 x SPC 25 

Screw of cover: 

Screw combi M5x25/10 (Z4) – 4.8 A2 

Tightening torque: 

-screw of cover - 3 Nm, 
-pressure nut of cable gland – 2,5Nm, 
-body of Ex e cable gland and plug – 3,5Nm, 
-screw of terminal pushbutton – 1,2Nm, 
-nut of operation heads – 2 Nm 

Dimension:  

128x100x111 mm 

Weight:  

cca 0,6 kg 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Switching capacity 

Rated operating voltage U

Rated operating current I

e

 

AC 5a 

230 V 

16 A for -20°C ≤ T

a

 ≤ +40°C 

15 A for -20°C ≤ T

a

 ≤ +50°C 

AC 5b 

230 V 

16 A for -20°C ≤ T

a

 ≤ +40°C 

15 A for -20°C ≤ T

a

 ≤ +50°C 

AC 1 

500 V 

16 A for -20°C ≤ T

a

 ≤ +40°C 

15 A for -20°C ≤ T

a

 ≤ +50°C 

AC 15 

250 V 

6 A for -20°C ≤ T

a

 ≤ +50°C 

500 V 

4 A for -20°C ≤ T

a

 ≤ +50°C 

DC 13 

  24 V 

6 A for -20°C ≤ T

a

 ≤ +50°C 

  60 V 

0,8 A for -20°C ≤ T

a

 ≤ +50°C 

110 V 

0,5 A for -20°C ≤ T

a

 ≤ +50°C 

Содержание SKX-SW/1

Страница 1: ...ied out under this user manual to provide and ensure safe operation within the nominal characteristics This user manual complement national Regulation and Standards The responsible person shall ensure their implementation Failure off implement this user manual can reduce explosion protection and endanger people property and the environment Any improper and illegal actions as well as non compliance...

Страница 2: ... force accordance to EN 60079 0 2012 therefore it has to be installed in places with lower risk of impact and additional clamping of the cable 5 DEGREE OF PROTECTION AND TECHNICAL DATA Certificate EXA 15 ATEX 0006X Marking 0722 Category and explosion protection II 2G Ex d e IIC T6 Gb Ambient temperature 20ºC Ta 40 50ºC Mechanical protection IP 54 Resistance to shock IK 08 Class of protection I PE ...

Страница 3: ... 8 ACTUATORS AND INDICATORS Operation heads type S6 92 01 and S6 90 02 manufacturer CZ Explosion proof Electric Appliances Co LTD category of explosion protected II 2 GD Ex e II Ex tD A21 IP66 examination certificate DNV 2009 OSL ATEX 46028U production quality assurance notification DNV 2008 OSL ATEX 38545Q Cable glands type SPU 25 manufacturer TEP Ex d o o Croatia category of explosion protected ...

Страница 4: ...losion protected II 2G Ex d e IIC Gb I M2 Ex d e I Mb examination certificate EXA 13 ATEX 0033U 10 MOUNTING Montage of installation switches is performed by fixing on a flat surface or wall with screw accessories in the tops of the rectangle at given dimensions 75 50 8 6 6 8 6 With the introduction of armored cables you need to connect an external ground wire to a metal glands and internal ground ...

Страница 5: ... repair or any other procedure are performed on the product by unauthorized person all producer responsibility for the product and the warranty and the manufacturer s declaration of conformity becomes invalid 13 RESPONSIBILITY AND AUTHORIZATION This instruction is the basic information about the product It is completed by the corresponding national laws and regulations Production use certification...

Страница 6: ...rska 69 Zagreb Croatia Made in Croatia SKX SW 1 Ui 690V Ith 16A 15A IP54 II 2G Ex d e IIC T6 Gb AC 5a AC 5b 230V 16A 15A EXA 15 ATEX 0006X 20 C Ta 40 50 C MA 0722 Medarska 69 Zagreb Croatia Made in Croatia SKX SW 2 Ui 690V Ith 16A 15A IP54 II 2G Ex d e IIC T6 Gb AC 5a AC 5b 230V 16A 15A EXA 15 ATEX 0006X 20 C Ta 40 50 C MA 0722 Medarska 69 Zagreb Croatia Made in Croatia SKX SW 6 Ui 690V Ith 16A 15...

Отзывы: