Programming Parameter:

3

+

SET

Press for 2 sec.

Upper Display

Enter 162 to pass to

parameters prog. mode.

SET

Inpt

Sensor Type (1)

SET

Back

P

re

ss

 “

B

ac

k”

 to

 r

et

ur

n

to

 th

to

of

 p

ar

am

et

er

s

pr

og

ra

m

m

in

bl

oc

k.

CodE

“tunE”

flashes

Enter 262 to

start

“auto-tune”

Upper Display

h-C

Select

Function (2)

SET

H.Hys/C.Hys

0..50 /

0.0 .. 5.0   (3)

o

C

SET

A.hys

1..50 /

0.0 .. 5.0   (3)

o

C

SET

Pb.C

10 .. 130   

o

C

SET

Ct

4..200 sec

SET

ti

0..30.0 min

SET

td

0..10.0 min

SET

UP.L

Lo.L ..

Upper Scale (

o

C)

SET

oFFS

-100 .. +100 /

-10.0 .. +10.0 (

o

C) (3)

SET

SET

AL.tY

Abs, rel, bnd, bn.i

-Abs, -rel, -bnd, -bn.i

SET

r.ALr/

b.ALr

-100.. +100 /

-10.0 .. +10.0 (

o

C) (3)

SET

C.dLY

0..30 sec

SET

P.Err

%0..100

SET

End Prog.

HeAt: 

Heating Function

Cool: 

Cooling Function

Heat/Cool Hysteresis 

o

( C):

PID is active if set to O

o

(for H.Hys)( C)

Alarm Hysteresis

o

( C)

o

Proportional Band in ( C)

Control Period (sec.)

Integral Time:

In minutes. If set to 0,

P, PD is active (integral OFF).

Derivative Time:

In minutes. If set to 0,

P, PI is active (derivative OFF).

C.Hys/

H.Hys

not 0

Upper limit value for Lo.L,

H.SET and A.SET. Upper Scale value

differs according to the selected

sensor type.

Offset Value; Offset is directly added

to the measured value. This feature shall

be used for user calibration. Normally set to 0.

LO.L

Lower Scale ..

UP.L (

o

C)

Lower limit value for UP.L,

H.SET and A.SET. Lower Scale value

differs according to the selected

sensor type.

Alarm Type:

Abs: Absolute,                 -Abs: Absolute, invert out

rel: Relative,                    -rel: Relative, 

bnd: Band,                        -bnd: Band, 

bn.i: Band inhibit,           -bn.i: Band, 

invert out

invert out

invert out

Relative or band Alarm Value.

Displayed if AL.tY is other then

Abs or -Abs.

Active only in cooling mode.

Minimum delay before OUT becomes ON

after it becomes OFF.

Determines the duty cycle of OUT output 

when “Fail” message is displayed. If 0, OUT is always OFF.

If 100, OUT is always ON, when device “fails”. Period is Ct.

(1) When sensor type is changed, Up.L, Lo.L, H.Set or A.Set may be set to a new value automatically, if any of 

then violates measuring scale of the selected sensor.

(2) ON-OFF control is only option for Cooling function.

(3) If sensor type is selected as Pt.0.

AL.tY=

Abs, -Abs

h-C=

heat

SET

J: J Type T\C, K: K Type T\C

T: T Type T\C,  S: S Type T\C

R: R Type T\C,  Pt: Pt100

Pt.0: 0.1  resolution Pt100

o

C

Factory Set 
Values:

H.Set: 100 

o

C

o

A.Set: 400  C
Inpt: J
H-C: Heat

o

H.hys: 3  C

o

A.hys: 3  C

o

Pb.C: 30  C
Ct: 4 sec.
ti: 5.0 min.
td: 1.0 min.

o

UP.L: 400  C

o

Lo.L: 0  C

o

oFFS: 0  C
AL.tY: rel

o

r.ALr: 3  C
C.dLy: 15 sec.
P.Err: 0

Auto Tune:

Before starting “Auto-tune”, adjust H.SET.

 “Auto tune” does not start in“cooling” mode.

Process value may exceed H.Set during 

auto-tune.
After auto-tuning, control form automatically

switches to PID mode.
Auto-tuning is stopped (interrupted) ant time

by pressing any key. In this case, the 

parameters before auto-tuning is valid.

Auto-tuning may not always determine the

best values for your process.

CodE

Enter 162