Testing Fuses and Bus Connectors

• 

Press SET and then press 

/

 to set emissivity to relatively high for paper covered 

fuse body or insulated connections.

• 

Press MODE to select MAX.

• 

Scan the paper covered length of fuse.

• 

Without releasing the trigger, scan each fuse. Unequal temperatures between fuses 

may indicate voltage or amperage imbalance.

• 

Press SET and then press 

/

 to set emissivity to relatively low, for metal fuses 

and caps and insulated bus connections.

Testing Electrical Connections

• 

Press SET and then press 

/

 to set emissivity to relatively low for uninsulated 

connectors or bus connections or relatively high for insulated connections.

• 

Scan the conductor, moving toward direction of electrical connector.

Note:

 conductors are typically smaller than the Thermometers spot size. If the spot size 

is bigger than the connector the reading is the average within the spot.

Scanning walls for air leaks or insulation deficiencies

• 

Turn off heating, cooling, and blower.

• 

Press SET to select emissivity. Use

/

to select emissivity relatively high for 

painted surfaces or window surfaces.

• 

Measure an interior partition wall surface temperature. Do not release the trigger. 

• 

Record this temperature as your baseline (or benchmark) for a “perfectly” insulated 

wall.

• 

Face the wall to be scanned.  Stand 1.5m away to scan a 5cm spot on the wall. 

Scan horizontal rows of wall from top to bottom, or horizontal rows of ceiling from 

wall to wall.   

Look for greatest deviations from baseline temperature to identify problems. 

• 

This completes the insulation test scan.

Checking Hydronic radiant heat applications

• 

Radiant heat tubes in the floor will normally run parallel to the outside walls.  

Starting at the floor wall juncture, scan parallel to the wall while moving into 

the room away from the wall.  Parallel to the outside wall you should find 

parallel isothermal rows indicating the location of heat tubes below the surface.  

Perpendicular to the outside wall, you should find rising and falling temperatures at 

equal distances.  High temperatures indicate you are scanning a heat tube beneath 

the floor surface, low falling temperatures indicate a space between the heat tubes.

Measuring Grille or Diffuser Discharge Temperature

• 

Press SET and then press / to select relatively high emissivity.

• 

Aim the Thermometer at the discharge air grille, register, or diffuser.

• 

Measure discharge temperature.

• 

Release trigger to freeze the temperature reading for 8 seconds and record this 

temperature. Grille, register, or diffuser temperature should be equivalent to 

discharge temperature at the air handler.

Testing Enclosed Relays

• 

Press SET and then press 

/

 to set emissivity to relatively low for uninsulated 

connectors or relatively high for plastic encased relays or for bakelite enclosed 

relays or insulated connectors. 

• 

Press MODE to select MAX. Start to scan.

• 

Measure the relay casing, looking for hot spots.

Содержание 72-8732

Страница 1: ...1 Model 72 8732 Infrared Thermometer ...

Страница 2: ...c electricity Thermal shock caused by large or abrupt ambient temperature changes allow 30 minutes for the Thermometer to stabilize before use Do not leave the Thermometer on or near objects of high temperature Replace the batteries as soon as the low battery indicator appears on the display Remove dead batteries from the Thermometer or if it is not going to be used for a long time Never mix old a...

Страница 3: ...inimum temperature anytime the display is on The MAX MIN temperatures are constantly calculated and updated while the trigger is pressed After the trigger is released all readings are held for 8 seconds Emissivity setting display Laser on symbol SCAN Active SCAN HOLD Display Hold MAX MIN Maximum or Minimum Value Low Battery symbol Appears when the battery charge is 4 5V Backlight indication o C o ...

Страница 4: ...er The Thermometer turns off when no activity is detected for 8 seconds To measure temperature aim the Thermometer at the target pull and hold the trigger Release the trigger to hold a temperature reading To find a hot or cold spot aim the Thermometer outside the target area Then slowly scan across the area with an up and down motion until you locate the hot or cold spot Distance and target spot s...

Страница 5: ...ou to adjust the unit s emissivity for the type of surface To adjust values for emissivity see table below 1 Press SET to select emissivity set up icon E on the display will flash The Thermometer steps through emissivity set up o C o F high low limit setting 2 Press to increase the value by 0 01 The maximum value is 1 00 3 Press to decrease the value by 0 01 The minimum value is 0 10 Measure Surfa...

Страница 6: ...l start flashing to allow you to allow or disable the high limit audible warning Press SET to enter the low setting MIN will flash on the display Select or to adjust in 0 1 degree increments Hold the adjustment button for a rapid incremental change The sounder indicator will start flashing to allow you to allow or disable the low limit audible warning When the sounder is active an intermittent sou...

Страница 7: ...zontal rows of wall from top to bottom or horizontal rows of ceiling from wall to wall Look for greatest deviations from baseline temperature to identify problems This completes the insulation test scan Checking Hydronic radiant heat applications Radiant heat tubes in the floor will normally run parallel to the outside walls Starting at the floor wall juncture scan parallel to the wall while movin...

Страница 8: ...95 500ms Distance to Spot 12 1 Emissivity adjustment 0 10 1 00 Laser Sighting Single point laser Power Class 2 Output 1mW wavelength 630 to 670mm Power Supply 6F22 9V Battery Power consumption Over 30hrs alkaline or over 10hrs gp Weight 0 322kg INFORMATION ON WASTE DISPOSAL FOR CONSUMERS OF ELECTRICAL ELECTRONIC EQUIPMENT These symbols indicate that separate collection of Waste Electrical and Elec...

Отзывы: