background image

Constant Voltage (CV), Automatic crossover & Constant Current (CC) 

 

The power supply functions as a constant voltage source (CV) as long as the load current is less than the preset current limiting 
value. When the load current is equal to or greater than the preset current limiting value, the power supply will automatically 
cross over to the constant current mode, voltage will drop, (CC) will show on the LCD display panel and it will operate as a 
constant current source. 
When the load current drops below the preset current limiting value, the supply returns to constant voltage (CV) mode. 

 

Set the Output Voltage and Presetting Current Limiting Value (CC) 

 

Push the knobs one time to check the preset voltage and current level. Push the knobs again until the decimal place which you 
want to adjust. The selected decimal place will flash. Turn the knobs to adjust your desired value. 
To check the preset voltage and current level, just turn the knobs lightly in any direction or just push the knobs one time. 

 

Connection and Operation Procedure 

 

1.  After checking with the rating label plug in to AC mains. 
2.  Switch on the power supply and the LCD display should be on at the same time. 
3.  The (CV) icon should be shown on the display. 

4.  Turn to current volume knob 

 to maximum clockwise if you do not require lower Current limiting value, otherwise do the preset the 

(CC) limiting procedure. 

5.  Set your desired output voltage and then turn off the output terminal by push button 

6.  Connect to your load positive to positive and negative to negative. 

7.  Turn on the output terminal again and check if display shows (CV). 

8.  If display shows (CC), either your preset current limiting value is too low or your load requires more voltage and current. You need to 

re-access the voltage and current requirement of your load and increase the voltage or current accordingly until (CV) appears. 

         

Tracking Output Over Voltage Protection (OVP) 

 

This is to protect the connected load in the event that  the  output voltage control circuit  mal-functions, the  maximum output 
voltage will not exceed 30% of the adjusted voltage value at the time of the operation. 

 

Over Temperature Protection 

 

When the temperature inside the power supply becomes higher than a pre-determined value, the output voltage and current of 
the  power  supply  will  automatically  decrease  to  zero  to  prevent  damage  to  power  supply.  When  the  temperature  inside  the 
power supply returns to about 65°C then the power supply will automatically return to operation again. 

 

 
SPECIFICATIONS 

 

 

72-8350A 

72-8345A 

72-8340A 

Input Voltage (Jumper Selection) 

90 - 130 / 180 - 264Vac , 50 / 60Hz~ 

Full Load Input Current at 120Vac 

1.9A 

Output Voltage Adjustable Range 

1.0 - 20Vdc 

1.0 – 36Vdc 

1.0 - 60Vdc 

Output Current Adjustable Range 

0 - 5A 

0 - 3A 

0 - 1.6A 

Voltage Regulation 

 

Load from 10% to 100% Variation 

120mV 

50mV 

50mV 

 

Line from 100 to 132Vac Variation 

20mV 

 

Ripple & Noise in r.m.s. 

5mV 

5mV 

8mV 

 

Ripple & Noise (peak to peak) 

30mV 

50mV 

100mV 

Current Regulation 

 

Load from 10% to 100% Variation 

20mA 

 

Line from 100 to 132Vac Variation 

20mA 

 

Ripple & Noise (peak to peak) 

70mA 

20mA 

20mA 

Switching Operation Frequency 

80KHz to 120KHz 

Power Factor 

0.65 

Efficiency at Maximum Power 

80% 

80% 

78% 

Volt and Amp Control Type 

Rotary Encoder 

Voltmeter and Ammeter Display 

4 Digit 

Voltmeter Accuracy 

±0.5% +5counts for range V≤5V  ±0.5% +5counts for range V≤10V  ±0.5% +5counts for range V≤20V 

 

 

±0.5% +3counts for range V>5V  ±0.5% +3counts for range V>10V  ±0.5% +3counts for range V>20V 

Ammeter Accuracy 

±0.5% +5counts for range I≤2A 

±0.5% +5counts for range I≤1A 

±0.5% +5counts for range I≤0.5A 

 

 

±0.5% +3counts for range I>2A 

±0.5% +3counts for range I>1A 

±0.5% +3counts for range I>0.5A 

LCD Indication 

CC, CV, Amp, Volt, Output ON-OFF   

Protection 

Short Circuit, Overload, Over Temperature, Tracking OVP 

CE Approvals 

LVD : EN 61010 , EMC : EN 55011 

Cooling System 

Natural Convection 

 

Dimensions in mm (WxHxD) 

70 x 150 x 250mm / 2.8 x 6.0 x 9.8in. 

Weight in Kg 

2Kgs / 4.4Lbs 

Remarks 

All the data are based on 120V 60Hz~ 

 

 
 
 
 