TemperZone OSA 220 Скачать руководство пользователя страница 1

OSA 220

Split System
Outdoor Unit

Installation &
Maintenance

REFRIGERATION PIPING

General

The OSA 220 is shipped with a refrigerant
charge sufficient for a 10 m line length.
The matched indoor unit is shipped with a
holding charge of nitrogen. OSA 220 units
have one flare and one brazed pipe
connection.

Recommended Pipe Sizes

Suction pipe :

28 mm OD

Liquid pipe :

13 mm OD

Line Lengths

For line lengths in excess of 30 m, fit a
compressor crankcase heater to prevent
liquid refrigerant condensing in the 'off'
cycle. Refer also to 

Oil Charge

 overleaf.

Maximum extended line length is 50 m.

Height Separation Limits

Reverse Cycle Systems

  Outdoor Unit above Indoor Unit : 12 m
  Outdoor Unit below Indoor Unit : 12 m

Cooling Only Systems

  Outdoor Unit above Indoor Unit : 18 m
  Outdoor Unit below Indoor Unit : 12 m

Vertical Risers

If the outdoor unit is to be installed above
the indoor unit, then the suction riser should
be trapped at the bottom of the vertical rise
and then again at 5 m (maximum) intervals.
This is to ensure oil return to the compressor.
The trap to be a 'swan neck' curve in the
pipe, with no change in the pipe size.

Piping

1.

Use clean sealed refrigeration grade
piping.

2.

Cut pipe with a pipe cutter ONLY.

3.

Use long radius bends (2x pipe dia.).

4.

Insulate the suction (gas) line and seal
all insulation joints.

5.

Filter dryer may be fitted in the liquid line
(bi-flow type on reverse cycle systems).

6.

Include a process point in the
interconnecting pipework.

7.

Ensure open pipe ends are sealed until
the final connection is made.

8.

Immediately before removing brazed
pipe connection's seal, reduce holding
charge between connection points and
service valves to atmospheric pressure.

Warning

:  Failure to do so may cause

injury.

continued...

When the unit is being installed on a roof it
is recommended that the unit is installed on
a substantial structure with vibration
isolating springs beneath the unit. These
springs are not supplied with the unit.

Wall Mounting Option:

Complete wall mounting instructions are
supplied with the optional wall mounting kit.

Drain

Install the unit with a positive fall to the rear
to ensure condensate and/or rain water
drains away freely through the drain holes
provided. For a totally drip free installation
mount the unit in a separate drain tray.

OPTIONAL FAN SPEED CONTROLLER

Fit a head pressure fan speed controller
where cooling is required in below 20

°

C

ambient conditions for long periods of time.
An electronic HP Fan Speed Controller
(4 amp) is available from 

temperzone

.

GENERAL
OSA

 

220

 - 

A general designation for outdoor unit

OSA

 

220C

Outdoor unit, cooling only version

OSA

 

220R

Outdoor unit, reverse cycle version

This OSA 220 Outdoor Unit must be
installed in accordance with all national and
local safety codes.

INSTALLATION

Positioning

Refer to dimension diagram below for
minimum clearances. Mount either free
standing or on a wall using the optional
mounting brackets available.

Free Standing 

:

Fasten the unit down to a firm flat horizontal
base using the four holes provided in the
mounting rails.

Dimensions (mm)

      OSA 220

Not to Scale

Net Weight

OSA 220C   147 kg
OSA 220R   151 kg

SERVICE

ACCESS

PANEL

580

MTG CTR

20 DIA.

ELECTRICAL

CONDUIT

HOLES

1030

OA

1140 OA

722 MTG CTR

10 DIA. SLOTS

140

200

20 DIA.
DRAIN
HOLE

595 OA

150 MIN.

 CLEARANCE

150 MIN. CLEARANCE

2000 MIN. CLEARANCE

REFRIG.
CONN'S

200

ELECTRICAL
ACCESS
PANEL

1000 MIN. CLEARANCE

150 MIN.

 CLEARANCE

20 DIA.
DRAIN
HOLE

20 DIA.
DRAIN
HOLE

PROJECTION