TemperZone OSA 160RKTGH Скачать руководство пользователя страница 2

UNIT CONTROLLER (UC7)   

The Unit Controller provides system 
protection functions such as coil frost 
protection, de-icing, high head pressure 
and low suction pressure cut-out.  It 
also protects against rapid cycling of the 
compressor(s) and loss of refrigerant. 
Various methods of head pressure control 
(or limiting) are employed in temperzone 
units. The particular method used varies 
from model to model, but is also handled by 
the Unit Controller. In combination, these 
features deliver optimised performance 
across a wide operating temperature range.
As a result of the UC’s control of these 

inter-related functions, the outdoor fans may 

take some time to start rotating after each 

compressor start. They may also run on 

when the compressor stops. The fans will 

stop during a de-ice cycle and the speed will 

vary either smoothly, or in steps, in order to 

protect against excessively low or high head 

pressure.
Refer to UC7 Controller label on the unit or 

www.temperzone.biz

 for operation & fault 

diagnostics information.

MAINTENANCE
Weekly For First Four Weeks

1.  Check indoor unit air filters (if fitted) and 

vacuum or wash clean as necessary.

2.  Check condensate drain for free 

drainage.

3.  Check compressor compartment for oil 

stains indicating refrigerant leaks.

4.  Check tightness of electrical 

connections.

Six Monthly

1.  Check the tightness of all fan and motor 

mountings.

2.  Check tightness of electrical 

connections.

3.  Check that fan motors are free running.

4.  Check suction and discharge operating 

pressures.

5.  Replace indoor unit air filters (if fitted).

6.  Check condensate drain for free 

drainage.

Yearly

1.  Check all refrigerant piping for chafing 

and vibration.

2.  Check the operation of electric heaters if 

fitted.

3.  Check air supply at all diffusers.

4.  Check for excessive noise and vibration 

and correct as necessary.

5.  Check for insulation and duct damage 

and repair as necessary.

6.  Remove lint and dust accumulation from 

outdoor coil fins. 

7.  Touch up any outdoor unit paintwork 

damage to prevent corrosion.

NOTE

The manufacturer reserves the right to 

change specifications at any time without 

notice or obligation. Certified dimensions 

available on request. 

Signal Input for Controller 0-10V is required 

(temperzone Part No. 201-000-386).
If a TZT-100 Controller is used then variable 

capacity control is automatically included 

and no additional wiring is required.

Note

: The TZT-100 Controller can 

automatically switch the indoor fan off during 

de-ice, if selected, therefore no additional 

wiring is required to achieve this result.
A 24 hour power supply to the crankcase 

heaters is required, otherwise the warranty 

is void.

SYSTEM CHECK TESTS

1.  Leave the remote switch in the off 

position and close the mains isolating 
switch.

 

A four hour delay period is required to 
allow the crankcase heater to drive any 
liquid refrigerant out of the compressor 
oil.

2.  Check that all fan motors are free 

running.

3.  Check for correct rotation of the 

compressor. If rotation is incorrect 

the compressor will not pump and will 

draw minimal current. To correct motor 

rotation, change the phasing at the main 

power terminal. 

4.  Check that the thermostat is correctly 

wired to the unit and is set at the desired 

temperature.

5.  Check that the indoor coil sensor lead is 

correctly wired to the unit.

6.  Check that the air filters, if any, have 

been correctly installed.

7.  Check any supply air diffuser dampers 

are open.

START UP PROCEDURE

Use the supplied Commissioning Sheet to 

help you complete the following procedure:
1.  Switch on the unit after the four hour 

delay period for the crankcase heater 

has expired. 

2.  Check the supply voltage.

3.  Measure the current draw on the 

compressor motor and on each fan 

motor. Check all readings against the 

specified values - particularly the indoor 

fan amps if the unit is installed in a free 

blow application.

4.  Fit gauges and measure the suction and 

discharge pressures.  

Important

: Gauges must be designed 

specifically for use with R410A.

5.  Test the operation of the high pressure 

safety control by switching off the 

outdoor unit's fan.

6.  Test the operation of the reversing valve 

by running the unit in both the heating 

and cooling mode.

7.  Check that the air flow over the outdoor 

unit's coil is adequate and that the fan is 

running smoothly.

8.  Check the superheat - refer charging 

procedure.

9.  Check the supply air flow at each outlet.

10. Touch up any outdoor unit paintwork 

damage to prevent corrosion.

Procedure:

1.  Evacuate Indoor Unit and 

interconnecting pipework to a pressure 

of 500 microns and hold for 15 mins. 

2.  Add refrigerant, if needed, via the 

Schraeder connection on the smaller of 

the Outdoor Unit's two service valves. 

3.  Open the service valve at the Outdoor 

Unit to allow refrigerant to flow 

throughout the system.

4.  Leak check all brazed and fitted joints.
IMPORTANT :

Step 8 of the 'Start Up Procedure' requires 

you to check that the superheat on the 

suction line (where it enters the Outdoor 

Unit) is between 3°C – 5°C on cooling cycle 

with an indoor air temperature in the range 

21° – 27°C and outdoor air temperature in 

the range 24° – 35°C. If the conditions of the 

day do not allow this, use the heating cycle  

or other heat source to raise the indoor 

air temperature to about 24°C. Return to 

cooling cycle and blank off the outdoor 

coil to raise the head pressure to 400 psig 

(2760 kPag). Alter charge up or down to 

establish correct superheat.

WARNING:

This unit is designed for use ONLY with 

the refrigerant HFC -410A. The use of 

other refrigerants is NOT authorised or 

approved by the manufacturer and may 

cause operational problems such as poor 

performance and efficiency, loss of capacity, 

degradation of materials and refrigerant 

leaks. 

The use of flammable or explosive 

materials as a refrigerant creates the 

additional risks of fire and explosion 

which may result in property damage, 

personal injury or death.

Oil Charge

For line lengths in excess of 40 m, Emkarate 

RL22CF polyolester oil (or similar) should  

be added to the refrigerant at the rate of  

10 ml/m of suction piping. 

Note

: Do not use 

mineral oil.

ELECTRICAL REqUIREMENTS

Electrical work must be done by a qualified 

electrician.  The outdoor unit must be wired 

directly from a distribution board by means 

of a circuit breaker or H.R.C. fuse, and a 

mains isolator provided - preferably close to 

the Outdoor Unit.

Note

:  DO NOT USE REWIRABLE FUSES.

Standard units are suitable for use with 

thermostats with either manual Heat/Cool 

selection or automatic changeover subject 

to the contact ratings of the thermostats. 
The matched ISD indoor unit is supplied 

with a 25m coil sensor lead that must be 

connected as per the wiring diagram.
The system is set up for the compressor to 

be controlled variably by:
1.  TZT-100 Controller (via modbus),
2.  0-10V dc command via BMS modbus, or
3.  0-10V dc command via a client supplied 

external controller. 

If option 3 is chosen, then the optional 

Pipe Length Capacity Loss

On Cooling Cycle Due to Pressure Drop
Note :  

Loss percentages are approximations only, due to piping variations.  No allowance made for vertical piping.

Pipe Size (mm)

Equivalent Line Pipe Length (m)

Liquid

13

Suction

22

5

0.7 %

22 mm

0.5 m

20

4.7 %

10

2.1 %

15

3.4 %

30 

6.1 %

Suction Pipe Size OD

Long 90° Radius (2 x pipe dia.)

Additional Pipe Length to allow per Bend

Отзывы: