TemperZone ISD 80K Скачать руководство пользователя страница 2

If the Electric Heater Box or Filter Box 
options are to be used, allow adequate 
clearance for servicing.

If low noise is a critical factor in the 
installation, refer to Figure 6 for noise 
isolation recommendations.

It is recommended that the unit be mounted 
using the spring mounting system, supplied 
as an optional extra (Fig.2). This system 
minimises transfer of vibration into the 
building structure.
If a more rigid installation can be tolerated, 
then suspend the unit from four threaded 
rods (not supplied) attached to the ceiling. 
Four 'L' shaped brackets are supplied on the 
unit to facilitate this method. These brackets 
must first be unscrewed, reversed and 
resecured to enable rod attachment. 

The unit has a built-in sloping drain tray, 
therefore mount it level.
When finally positioned, tighten the lock 
nuts on the mounting rods from above and 
below the mounting flange to give a firm 
installation (see Fig. 3).

Condensate Drain
The condensate drain should be trapped 
outside the unit cabinet. The trap should 
have a vertical height of at least 50 mm.  
The drain should have a slope of at least 
1 in 50 and must not be piped to a level 
above the unit drain tray. (Refer Fig.4).

For long condensate pipe runs, fit a vent 
pipe near the drain trap. The top of the vent 
pipe must be at least 100 mm above the ISD 
unit's drain tray. 

It is essential that the drainage system 
for the evaporator is checked by pouring 
water in the drain tray and seeing that it 
discharges at the end of the drain and does 
not overflow the drain tray.

Note:  The built-in drain tray can be 
removed for cleaning (or fan access) by first 
removing the unit's base.

INDOOR–OUTDOOR UNIT
CONNECTIONS
Refer to the relevant OSA Outdoor Unit 
'Installation & Maintenance' pamphlet for 
piping instructions.  For wiring connections, 
refer to the Outdoor Unit wiring diagram in 
conjunction with the ISD wiring diagram in 
this pamphlet.

REFRIGERATION PIPING
Pipe Connection Sizes
 (mm OD) & Type
  Model 

Liquid 

Suction

  ISD 80K 

10 (

3

/

8

") sweat  16 (

5

/

8

") sweat

  ISD 95K 

10 (

3

/

8

") sweat  16 (

5

/

8

") sweat

  ISD 110K  10 (

3

/

8

") sweat  19 (

3

/

4

") sweat

  ISD 140K  10 (

3

/

8

") sweat  19 (

3

/

4

") sweat

The ISD is shipped from the factory with 
a pressurised holding charge of nitrogen.  
Immediately before removing any brazed 
pipe connection's seal, reduce the holding 
charge to atmospheric pressure. 
Warning: Failure to do so may cause injury.

Refer to the Outdoor Unit 'Installation & 
Maintenance' pamphlet for evacuation 
procedure and piping requirements.

ELECTRICAL WIRING
The electrical supply required (via the 
Outdoor Unit) is specified on the Outdoor 
Unit's wiring diagram.

Electrical work must be carried out by a 
qualified electrician in accordance with local 
supply authority regulations and the  wiring 
diagram.

In a free blow or low resistance application,  
beware of exceeding the fan motor's full 
load amp limit (refer Outdoor Unit's wiring 
diagram).
Note: The SAT-2 Controller automatically 

switches the indoor fan off during de-ice, 

therefore no additional wiring is required to 

achieve this result.

INDOOR FAN SPEED
The fan speed can be set to LOW, MED, or 
HIGH - whichever best suits the application.
If the air returning to the indoor unit is 
regularly expected to be above 50%RH, 
then the coil face velocity should be limited 
to be 2.5 m/s or less (refer Air Handling 
graph in Technical Data pamphlet). 
High humidity levels can occur in tropical or 
subtropical conditions, and/or when heavily 
moisture laden fresh air is introduced. Select 
a fan speed that avoids water carry-over 
problems.

SAT-2 CONTROLLER
The following components are supplied in a 
box taped inside the return air spigot:
1.  SAT-2 Wall Control plaque, including wall 

mounting plate.

2.  10 m interface lead (electrical box-to-

plaque).

3.  User's Operating Instructions booklet.
4.  Lithium CR2032 battery (3V).
Optional
1.  Remote return air sensor (in box). 
2.  Remote return air temperature sensor 
  lead; 1.5, 6, 12 or 25 m. 
3.  20 m extended interface lead 
  (electrical box-to-plaque).
4.  ISD indoor unit–to–OSA outdoor
  unit interconnecting lead;  
  12.5 m or 25 m; 7 core. 
5.  SAT-2 Zone Control PCB. 
6.  Zone Control 24V transformer.
7.  Additional SAT-2 Wall Control plaque.
8.  Infra red remote control.

Installation
The SAT-2 Controller PCB is supplied pre-
installed in the ISD unit's electrical box.
1.  Isolate the ISD unit from power supply, 

then remove electrical box cover.

2.  Remove the SAT-2 box supplied taped 

inside the return air spigot.

3.  Remove the Wall Control's interface 

lead from this box and connect the bare 
wired end of the interface lead to the 
terminal block on the SAT-2 Controller 
board (refer wiring diagram). Trace the 
remaining length of the lead to the Wall 
Control's intended location. 

4.  Remove the Wall Control's backing plate 

by using a small screw driver to remove 
the single screw at the bottom edge of 
the plaque.

5.  Install the Lithium battery, supplied loose, 

positive (+) side up in the Wall Control's 
battery holder. 

6.  Check the wall where the Wall Control 

plaque is to be located is flat before 
fastening the wall mounting plate. 

  Alternatively, the mounting plate can 

be screwed to a standard wall socket 
mounted horizontally. 

 

Note:  Use low profile (mush) headed 
screws to prevent contact with the PCB 
board. Fixing the plate to a distorted 
surface may damage the control.

7.  Drill hole in wall to allow cable entry.
8.  Connect the interface lead's lugs to the 

Wall Control board as per the wiring 
diagram overleaf. 

9.  Ensure the interface lead is run 

separately and away from main 
power supply wires, including the 
interconnecting cable. When installing 
cabling, trim any excess length to suit 
your location. 

10. Fill around the interface lead with foam 

or cover hole with PVC tape to prevent 
draft from wall cavity affecting control 
operation. Do not use aluminium duct tape.

11. Secure the Wall Control body to the 

mounting plate by replacing the locking 
screw removed earlier.

12.Replace the ISD electrical box cover.

Remote Air Temperature Sensor/s 
(option)
The air temperature sensor is by default 
located in the Wall plaque. Optional remote 
air temperature sensors are available so that 
the measurement of the room temperature 
can be taken away from the wall plaque, 
eg. elsewhere in the room or in the return 
air duct. 
Remote sensor's can be plugged directly 
into the Controller board (PCB). This 
board accepts up to four sensors which 
are designated as 'zones' one to four. The 
first return air sensor will automatically 
replace the Wall Control sensor and should 
be located in the same room as the Wall 
Control. The Controller will always use the 
average of the zones selected. Refer to the 
separate installation instructions supplied 
with the PCB for further details. 
Ensure all remote sensor wires are run 
separately and away from main power 
supply wires, including the interconnecting 
cable. 
 

SAFETY DRAIN TRAY
The safety drain tray is best secured to the 
ISD unit 

after the unit has been suspended 

in the ceiling, however it is possible to fit it 
before if circumstances make this easier.
1.  Unscrew the supporting brackets from 

their temporary shipping position, inside 
the drain tray, and retain the screws.  

2.  The drain tray has pre-drilled holes 

designed to align with the screws on the 
unit. One at a time, remove a screw from 
each bottom corner of the ISD unit and fit 
a bracket using the same screws. 

3.  Position the drain tray’s pipe exit so it is 

at the same end as the ISD unit’s drain 
pipe exit. 

4.  Supporting the drain tray from 

underneath, then secure the drain tray to 
each bracket using the supplied screws.

cont'd...

Отзывы: