background image

MAGIC II 

Training Guide – 11/14 

 

Page 1  

 

 

MAGIC II  

Installation and Calibration

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

INSTALLATION  

 

Leave all shipping braces in. Bolt down with 1/2-13 x 1 3/4 long screws. Then start up as 
follows: 

1.

 

Install clean sensor and new ceramic-coated shaft.  

2.

 

Connect motor power and check rotation.  

      Clockwise - Looking from the top of the 

MAGIC II

.  

3.

 

REMOVE

 vent

 screw

 in oil filled dampener. 

4.

 

Connect 24-35VDC power. Power (+) to 

Magic II (+)

, the load resistor in the (-) leg. 

5.

 

Connect digital voltmeter to front panel test points.  

With motor off

, adjust 

Coil

 to 

DC voltage marked on S/N tag Magic box.  

6.

 

Use 

HART

 Communicator to set the Upper Range Value (URV) and Lower Range 

Value (LRV) to match control rooms settings.  

7.

 

TEMCO has preset the curve for your consistency application. 

8.

 

Electronic dampening is factory preset – Do Not Change. 

9.

 

Switch 

HART 

to read Process Variable.    

10.

 

Move torque arm, DC voltage should swing between 6.0 and about 7.0 volts and 
Consistency should follow DC voltage swing. 

11.

 

 Remove volt meter & Hart Communicator.   

12.

 

Grease Cartridge Option – Install elbow and thread on cartridge to activate. 
 

 

 

Содержание MAGIC II

Страница 1: ...leg 5 Connect digital voltmeter to front panel test points With motor off adjust Coil to DC voltage marked on S N tag Magic box 6 Use HART Communicator to set the Upper Range Value URV and Lower Range Value LRV to match control rooms settings 7 TEMCO has preset the curve for your consistency application 8 Electronic dampening is factory preset Do Not Change 9 Switch HART to read Process Variable 1...

Страница 2: ...mmunicator and then go to the LRV and URV screen 2 Set the Lower Range Value LRV to match control room setting 3 Set the Upper Range Value URV to match control room setting FIRST TIME ZERO ADJUSTMENT 1 Put Consistency Loop in Automatic Control 2 Obtain a Lab Sample Record the MAGIC s signal at the time the sample is taken 3 Adjust Coil so the MAGIC s signal agrees with Lab Sample SN Tag w Coil Vol...

Страница 3: ...MAGIC II Training Guide 11 14 Page 3 MAGIC CURVE SELECTION Furnish MAGIC II Curves Unbleached Stock 10 OCC and Bleached 7 TMP and Newsprint 6 The curve is factory preset for your application ...

Страница 4: ... refer to Ouput Adjustments to change zero Varying error with changes in consistency Refer to Output Adjustments to change sensitivity with the Curve Number MAGIC output does not change Voltage can vary 05 VDC Verify that breather plug on damper has been removed Verify that shipping brace has been removed Examine area around torque arm and motor for objects obstructing free movement Disconnect loo...

Страница 5: ...late 20mA output ____VDC 20mA 5 Check Coil Voltage with MOTOR OFF ____VDC 6 Does Coil Voltage go UP when torque arm is pushed to the right and DOWN when pushed to the left ____ Yes ____ No 7 Does Consistency Output follow the coil voltage changes ____ Yes ____ No 8 Disconnect ThermaCoil from electronics enclosure Does Coil Voltage equal approximately 10vdc ____ Yes ____ No TEMCO Engineering Inc 16...