TG-7 Cellular Series Installation & Operating Guide
3
56053501 Rev A © 2022 Telguard
Information Related to Software Settings Fire Systems
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
FIRE SYSTEM INSTALLATIONS IN THE UNITED STATES: This product incorporates field-programmable
software. In order to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or
not used at all as indicated below.
Program feature or
option
Permitted
in UL 864
(Y/N)
Available settings
Settings permitted in
UL 864
Link Supervision when
used as a Sole Path
Y
Disabled, 200 seconds, 5
minutes, 60 minutes
200 seconds, 5 minutes,
60 minutes
Automatic Self-Tests
when used with an
alternate communication
path
Y
Disabled, 6 hours*, Daily,
Weekly, Monthly
6 hours
AC Failure Condition
(ACFC)/Low Power
Failure (LPF)
Y
Disabled, any number of hours
up to 24
1 hour, 2 hours, 3 hours
No Service Condition
(NSC) delay
Y
30 seconds, 60 seconds, 3-, 5-,
10- 20-, 30-, 45-, 60-, 1440-
minutes
30 seconds, 60 seconds,
3 minutes
*
6 hours is specified in 2013 and later editions of NFPA 72; the 2010 edition specified 24 hours (daily).