TG-7 Dual Path Series Installation & Operating Guide
5
56052601 Rev B © 2022 Telguard
Information Related to Software Settings Burglary Systems
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
BURGLARY SYSTEM INSTALLATIONS IN THE UNITED STATES: In order to comply with the
requirements in the Standard for Central-Station Burglar-Alarm Units, UL 1610 and Standard Line
Supervision, the communicator must meet these requirements:
The TG-7 Dual Path Series communicator must be used in one of the following configurations:
•
As a primary communicator, single line-200 second supervision; or
•
As a secondary communicator line for a DACT (supervision not required). Every 24 hours, a check-in
signal must be sent from the communicator to the central station over the primary dialer and each
communication path shall be monitored for integrity (DACT shall have line monitoring enabled and the
communicator shall have cellular connection supervision enabled).
Additionally:
•
When the heartbeat transmission over the LTE-M network is enabled, the communicator can provide
Standard Line Security over the LTE-M channel.
•
The communicator shall be connected to a UL Listed alarm control panel.
•
A tamper switch on the communicator shall be connected directly to an input zone on the control panel,
and the zone shall be designated as the zone for Tamper Protection. Tamper wires and all other wires
connecting the communicator to the panel shall be in rigid or flexible metal conduit unless supervised.
•
The PPF panel presence failure feature must be enabled if the wiring distance between the panel and
the communicator is greater than 20 feet or the connection is not mechanically protected; setting is
accessible in the online portal.