SIMPO - BASIC INFORMATION
Page 29 of 48
Simpo Addressable Panel
- Подменю Self Addressing ще изглежда по следният начин и ще има следните функции:
S E L F A D D R E S S I N G - A D D D E V I C E . . .
D E V C O U N T : L 1 : 0 2 4 L 2 : 0 4 4
N E X T : 0 2 5 N E X T : 0 4 5
L O O P 1 -
L O O P 1 +
L O O P 2 -
L O O P 2 +
Menu Start Self addressing will auto address new devices for the system. The procedure will auto
start when the user enters the menu. New added devices will automatically receive address from
the system and will be auto saved.
If the procedure is interrupted from the installer or by other technical reason (power supply loss), it
could be started again from the same menu and the new added device will take the first empty
address, after the last saved. Addresses which are existing for the system has to be skipped.
The addresses which are skipped will stay empty till filling off all upper addresses and after that
the system will start rolling them again and it will start from the lowest address which is empty.
During the auto addressing an address could be skipped with manual command via the arrows in
the NEXT box.
The procedure will be active till its manual stop or after 30 minutes of no new devices added.
The menu will have a counter of the devices for every loop, which will auto update during the
procedure.
An indication for successful addressing from the detector will be the following: The detector will
power on it’s LED indicator for 2 seconds and after that it will go in normal mode.
2.5.5) Menu Panel Outputs:
menu for configuration of outputs Fire, Fault, Sounder and the
programmable outputs.
I N S T A L L E R A C C E S S L E V E L
4 ) A D D R E S S I N G
5 ) P A N E L O U T P U T S
6 ) G E N E R A L S E T T I N G S
I N S T A L L E R A C C E S S L E V E L
S e l e c t P a n e l O u t p u t
! ( L O O P S O U N D E R S W I L L F O L L O W S O U N D E R O U T )
S O U N D E R
E X T I N G U I S H
F I R E
M O R E > >