INDEX
Automatic power factor correction panels Pages 2 – 6
Power factor regulator
Pages 7 – 16
Wiring diagrams
Pages 17 – 21
GENERAL INFORMATION
Attention!!! Proper connection and start-up of power factor correction equipment is relatively simple yet it must not ever, under any
circumstances, be left up to chance. Consequently, the device will not engage or disengage the batteries of capacitors or it will
operate anomalously. In that these panels have all been tested and inspected by the manufacturer, any anomalous operation will be
due to faulty connections, and in particular or to a faulty positioning of the current transformer. Therefore, we kindly request that you
observe the instructions in this manual and rigorously follow them in the sequence indicated. Thank you for your kind attention and
collaboration.
Locate the panel in a well aerated space and far from any heat sources: good air circulation is one of the most important factors for
proper and long lasting operation. Leave at least 30 cm of space around the panel, so that air may freely enter and exit the area. Do
not locate the equipment in humid areas unless it has been specifically requested with a particular protection grade.
1- LOCATION OF THE EQUIPMENT
Operational limits:
-
Relative humidity: max 50% at 40° C – 90% at 20° C
-
Altitude: max. 2000 metres a.s.l.
-
Transport and warehousing: temp.-25 to +55° C