  Rev  1.01   Date  4.2.2020 

        Page 

4  of 7   

3.2  Installation  

3.2.1  Programming of the device address  

Burn the address of the horn/strobe horn to the device's card. Use the wire supplied with 
the software 

 PROG-4000 or the technician kit  TFC-7000 and connect the gator clips to 

lug 1 (positive) and 2 (negative).  

 

Note 

    

Burning an address to the base sets the address of the horn/strobe horn only. 
The detector installed on the base uses its own address and the setting of the 
device on the panel.  

 

3.2.2  Device settings on the panel  

Set the assembly on the panel to "Silenced Horn". When this option is selected, the horn 
will be off.  

On the 

 TFB-180BSA, setting the panel to Silenced Horns will disable the horn, but the 

strobe light will continue to be on, until Respond is pressed in the panel. 

Set the operating matrix of the device in the panel. Read the technical instructions of the 
panel for additional instructions about setting the devices and operating matrix.  

 

3.2.3  Configuration switches  

   TFB-180BA 

 

Note 

    

The switch is set to 1 when the selector is close to 1, and to 0 when the 
switch is away from 1 (OPEN state).  

 

Switch 

3  

Switch 

Switch 

3  

Sound 

Constant - 

 910Hz 

Goes up from 500Hz to 1,200Hz for 3.5 sec; stops for 
0.5 seconds 

Switches between 910Hz and 685Hz at a rate of 2Hz 

Intermittent sound, half a second at 910Hz, half a 
second off  

Goes down from 1,200Hz to 500Hz every second  

Sounds three pulses of 500mS at 

 910Hz and then 

goes off for 1.5 seconds  

Goes up and down every 0.5 second in the range of 
800Hz 

– 1,000Hz 

Goes up from 800Hz to 970Hz every second  

 

Содержание TFB-180BSA

Страница 1: ...d with a addressable horn strobe horn Technical instructions TELEFIRE GAS AND FIRE DETECTORS LTD P O Box 7036 Petach Tikwa 49250 Tel 03 970 0400 Fax 03 921 1816 Email info telefire com www telefire co...

Страница 2: ...i Note The equipment must not be installed operated or maintained before reading this manual and understanding its content 2020 2019 ALL RIGHTS RESERVED TO TELEFIRE GAS AND FIRE DETECTORS LTD...

Страница 3: ...the following panels ADR 7000 SAVER 7000 GUARD 7 ADR 3000 ADR SAVER 2 2 Detectors The addressable strobe horn and horn serve as a basis for the following detectors TFO 480A TFH 280A TPH 482A 3 Install...

Страница 4: ...he cable resistance as measured in the field has to be taken into account In communication lines for addressable devices SLC the loop resistance and capacitance the stricter of the two has to be consi...

Страница 5: ...to the grounding by the grounding clamps on the panel 3 1 5 Location The device has to be installed indoors Exposure to outdoor and weather conditions must be prevented to avoid high humidity or dust...

Страница 6: ...Horns will disable the horn but the strobe light will continue to be on until Respond is pressed in the panel Set the operating matrix of the device in the panel Read the technical instructions of th...

Страница 7: ...TO TELEFIRE GAS AND FIRE DETECTORS LTD Rev 1 01 Date 4 2 2020 Page 5 of 7 3 2 4 Configuration switches TFB 180BSA i Note The switch is off when the selector is close to the digit and on when the swit...

Страница 8: ...vice to the communication line of addressable devices and 24Vdc input i Note Measure the wiring to ensure there is no short circuit or connection or leakage to the ground before connecting the device...

Страница 9: ...ation panel or addressable output assembly 24 Vdc 4 1 TFB 180SA Maximum current consumption device line 180 A quiescent state 2 mA alarm state Maximum current consumption from 24Vdc power source 10 mA...

Отзывы: