Telect GMT Series Скачать руководство пользователя страница 11

© Telect, Inc.  All rights reserved. 3.6.17 v.2

1.509.926.6000  ::  telect.com

Low-Current 20/20 GMT Series Fuse Panels

Power :: Models 06004-01 & 06004-11 Installation Guide 

8

19. Check voltage and polarity 

at the input connectors of the panel. 

Also, check that:

•  The 

A

 LED on front of the panel turns on (green)

•  The 

B

 LED must remain red

If the 

A

 LED doesn’t turn green, recheck polarity at input connectors.  

(Reversing input connections will not harm the panel.) However, if the input  

power leads were reversed, the fuse fail relay will fail to energize, causing  

the normally open contacts to remain closed and normally closed contacts to  

remain open. If necessary, check across the FAIL RELAY alarm pins located  

on the rear of the panel as shown in Figure 9.

20. On the rear of the panel, with 

A

 LED lit (normal operation), but with 

LED off  

(failure operation), test the Side-A FAIL RELAY pins:

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NC

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NO

21. Conversely, when testing the Side-B pins:

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NC

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NO

22. Repeat Steps 18 to 21 for Feed B and observe that the 

B

 LED turns green. Across all FAIL  

RELAY alarm pins:  

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NC

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NO

23. For output wiring, strip off ¼ in. (~7 mm) of insulation. 

 

Like the input terminals, the output terminals are screw-tight, wire-clamping. The output terminals 

will accommodate 14-AWG to 6-AWG conductors. Like the output terminals, stranded wires  

for outputs should be tinned. 

Remember: output conductors must be rated at or above the amperage rating of the GMT fuse. For example, use no 

smaller than #16-AWG output wiring for 10A output fuses. Do not exceed 8A continuous load for a 10A fuse.  

 

 

 

 

Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52

www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 130358-2 A0.1

Page 8

19. Check voltage and polarity 

at the input connectors of the 

panel

. Also, check that

• The

 A 

LED on front of the panel turns on (green).

• The

 B 

LED must remain red.

If the 

A

 LED doesn’t turn green, recheck polarity at input con-

nectors. (Reversing input connections will not harm the pan-

el.) However, if the input power leads were reversed, the fuse 

fail relay will fail to energize, causing the normally open contacts to remain closed and nor-

mally closed contacts to remain open. If necessary, check across the FAIL RELAY alarm pins 

located on the rear of the panel and shown in Figure 9.

20. On the rear of the panel, with 

A

LED lit (normal operation), but with 

B

LED off (failure opera-

tion), test the Side-A FAIL RELAY pins.
• Expect continuity (0

Ω

) between Terminals 

C

 and 

NC

.

• Expect an open circuit (

∞Ω

) between Terminals 

C

 and 

NO

.

21.  Conversely, when testing the Side-B pins,

• Expect an open circuit (

∞Ω

) between Terminals 

C

 and 

NC

.

• Expect continuity (0

Ω

) between Terminals 

C

 and 

NO

.

22. Repeat Steps 18 to 21 for Feed B and observe that the 

B

LED turns green. Across all FAIL 

RELAY alarm pins 
• Expect continuity (0

Ω

) between Terminals 

C

 and 

NC

.

• Expect an open circuit (

∞Ω

) between Terminals 

C

 and 

NO

.

23. For output wiring, strip off ¼ in. (~7 mm) of insulation.

Like the input terminals, the output terminals are screw-tight, wire-clamping. The output ter-

minals will accommodate 14-AWG to 6-AWG conductors. Like the output terminals, stranded 

wires for outputs should be tinned. 

Remember: output conductors must be rated at or above the amperage rating of the GMT fuse. 

For example, use no smaller than #16-AWG output wiring for 10A output fuses. Do not exceed 

8A continuous load for a 10A fuse.

ALERT

!

ALERT!  GMT fuses have a small inherent electrical resistance resulting in a small inher-

ent power loss. For this reason, the GMT fuse manufacturer recommends that the load for 

GMT fuses up to and including 7.5A not exceed 80% of the fuse rating and that the load for 

10A GMT fuses not exceed 70% of the fuse rating. (For example, 10A fuse x .70 = 7A max. 

load). 

Total load for all GMT outputs on each side

 must not exceed 20A for a panel 

without

a fail-safe circuit, or 15A for a panel 

with

 a fail-safe circuit.

FAIL

RELAY

NO C NC

A

B

NO C NC

Figure 10 - Fail Relay 

Alarm Pins

Figure 10 - Fail Relay

Alarm Pins

ALERT

!

ALERT! GMT fuses have a smaller inherent electrical resistance resulting in a small inherent pow-

er loss. For this reason, the GMT fuse manufacturer recommends that the load for GMT fuses up 

to and including 7.5A not exceed 80% of the fuse rating and that the load for 10A GMT fuses not 

exceed 70% of the fuse rating. (For example, 10A fuse x .70 = 7A max. load). 

Total load of all GMT 

outputs on each side 

must not exceed 20A for a panel 

without

 a fail-safe circuit or 15A for a panel 

with 

a fail-safe circuit.

Содержание GMT Series

Страница 1: ... Telect Inc All rights reserved 6 17 v 2 1 509 926 6000 telect com Low Current 20 20 GMT Series Fuse Panels Power Models 06004 01 06004 11 Installation Guide ...

Страница 2: ...ossible in network connectivity and power management Founded in 1982 Telect is driven by the principles of innovation and customer service Headquartered in Liberty Lake WA the privately held company supports a global network of customers with a comprehensive product portfolio and a values driven corporate culture Our products and solutions are found across communications service provider networks ...

Страница 3: ...igure 1 Model 06004 1 Figure 2 Front View 1 Figure 3 Model 06004 01 Rear View 2 Figure 4 Model 06004 11 Rear View 2 Figure 5 Panel with Mounting Brackets in Stowed Position for Shipping 5 Figure 6 Bracket Installation Examples 6 Figure 7 Mounting the Panel 6 Figure 8 Connecting the Lug to the Rear Panel 7 Figure 9 Inserting Conductors 7 Figure 10 Fail Relay Alarm Pins 8 Figure 11 Designation Card ...

Страница 4: ... 3836 37 52 www telect com 2010 Telect Inc All Rights Reserved 130358 2 A0 1 Page 1 1 1 Overview Telect s 1RU Traditional Low Current GMT Series Fuse Panels provide pro tected secondary 24 Vdc to 48 Vdc power distribution to telecommunica tions equipment at the bay level Fuse panels are available for GMT outputs up to 10A per position in dual circuit panel configurations having 20 GMT fuse positio...

Страница 5: ... interior wiring DO NOT REMOVE CAPS or LOOSEN CLAMPING SCREWS Figure 3 Model 06004 01 Rear View Plastic Caps Caution Do not reverse polarity Alarm Pins for Circuits A B Screw Tight Wire Clamping Output Terminals Plastic caps cover screw tight terminals used by the manufacturer for installing interior wiring DO NOT REMOVE CAPS or LOOSEN CLAMPING SCREWS A B A B Screw Tight Wire Clamping Input Termin...

Страница 6: ...AWG no insulation AMP 35771 12 10 AWG no insulation Material Cold rolled steel powder coat telcom grey See 1 7 Schematics on page 12 for complete dimensions Screws with cross recessed heads Custom color finish available Mechanical Specifications Input terminals Type Screw tight wire clamping Wire 14 to 6 AWG copper wire Torque 16 in lb 1 80 N m max Output terminal Type Screw tight wire clamping Wi...

Страница 7: ...oad Percentage of full load heat dissipation at nominal voltage Less than 1 of total load wattage Reliability MTBF 200 000 hr 1 3 Inspection Please read these instructions carefully before beginning installation If you need assistance call Telect at 509 926 6000 or email Telect at getinfo telect com Inspect equipment after unpacking and compare it to the packing list Immediately report any shippin...

Страница 8: ...836 37 52 www telect com 2010 Telect Inc All Rights Reserved 130358 2 A0 1 1 4 Installation ALERT ALERT Install this product within a restricted access location where access is through the use of a tool lock and key or other means of security and is controlled by the authority responsible for the location Only qualified personnel may install and maintain this product ALERT ALERT Verify all connect...

Страница 9: ...RT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV etc 7 For ground wiring use a listed approved crimping tool to attach a listed approved single hole compression lug suitable for a 10 5 mm screw onto a suitable ground wire Bracket for a 19 in Rack Bracket for a 23 in Rack Flush Mo...

Страница 10: ...conductors at the bottom of the screw tight terminals as shown on the right 15 Tighten screws to 16 in lb 1 80 N m Telect Inc USA 1 509 926 6000 Mexico 52 33 3836 37 52 www telect com 2010 Telect Inc All Rights Reserved 130358 2 A0 1 Page 7 Ground wire should be same gauge as the input wir ing Input wire size depends solely on input interrup tion device at the primary power distribution unit 8 If ...

Страница 11: ...ads were reversed the fuse fail relay will fail to energize causing the normally open contacts to remain closed and nor mally closed contacts to remain open If necessary check across the FAIL RELAY alarm pins located on the rear of the panel and shown in Figure 9 20 On the rear of the panel with A LED lit normal operation but with B LED off failure opera tion test the Side A FAIL RELAY pins Expect...

Страница 12: ...tage and polarity at input of loads 30 After all designated GMT fuses have been installed check that the A and B LEDs are still green If an output fuse blows the corresponding A or B LED will turn red if an input fuse blows the corresponding A or B LED will be orange or amber Again test FAIL RELAY alarm pins on rear of the panel As before Expect continuity 0Ω between Terminals C and NC Expect an o...

Страница 13: ...e B Model 06004 11 contains the standard alarm relay plus an auxiliary relay AUX RELAY that can be triggered externally All relays have two sets of Form C dry contacts for wiring to audible and visual alarm indicators Audible and or visual failure indicators can be wired to the alarm pins in several ways 1 5 1 Standard Alarms When an input or output fuse blows the relay is de energized and the nor...

Страница 14: ...A GND IN FA 24 48V IN NO C NC A B NO C NC Auxiliary Relay Trigger Auxiliary Relay Contacts FA GND IN FA 24 48V IN Nomenclature is for contacts NEG or GND trigger POS or GND trigger Internal Wiring FAIL RELAY NEG or GND GND or POS External Alarm Device External Alarm Device FA AUX RLY FA AUX RLY FA GND IN FA 24 48V IN NO C NC A B NO C NC Auxiliary Relay Trigger Auxiliary Relay Contacts FA GND IN FA...

Страница 15: ...ses order 101557 For GMT safety splash splatter covers order 116915 1 7 Schematics 1 6 GMT Fuses Order E70319 001RC for each X 1 20A 250V input fuse For dummy fuses order 101557 For GMT safety splash splatter covers order 116915 1 7 Schematics GMT Fuse Part Numbers GMT Fuse GMT Fuse Part Numbers GMT Fuse 18A Yellow YEL 130781 2 5A White Orange WHT ORN 130783 A Violet VIO 100151 3A Blue BLU 004012 ...

Страница 16: ...of others This document and the products described herein are subject to change without notice POW ER A 1 5 10 15 20 POW ER B 1 5 10 15 20 A B FAIL SAFE A B ALARM FAIL SAFE Applies only to M odel 06004 11 FA AUX RLY FA AUX RLY FA GND IN FA 24 48V IN FAIL RELAY NO C NC A B NO C NC A B 24V TO 48V RTN FAIL RELAY NO C NC A B NO C NC A B 24V TO 48V RTN 23 02 584 6 19 00 482 6 22 31 566 7 18 31 465 1 1 ...

Страница 17: ...that the Hendry Telephone Products Power Distribution and Fan Panels conform to the protection requirements set out in article 4 of EMC Directive 89 336 EEC as per EN 55022 94 with A1 95 A2 97 class A EN 61000 3 2 95 EN 61000 3 3 95 EN 300 386 V1 2 1 00 03 and ETS 300 132 2 and in accordance with the Agreement on Mutual Recognition between the United States of America and the European Community Se...

Отзывы: