Subject to modifications and errors
Page 35 of 71
2019-06-26 edition
3.7.6
VDE-AR-N 4110 (tested according to TR3, evaluation report TR8)
Connection Mode
Conformity Range
Possible Range
ID
Default
.003
Connection
4-wire (LN)
3-wire, 4-wire (LN)
2-wire, 3-wire, 4-wire (LN),
4-wire(LN+LL)
Nominal Voltage
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.005
ULN/LL nom
Unom Y
Unom Δ
V
V
230.0
400.0
57,5
100.0
230.0
400.0
28,8
50.0
241.4
420.0
Overvoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.011
ULL > off
U
THR
OFF
%Unom
110
100
130
100
135
U
THR
ON
Fixed Hysteresis (1% U
NOM
)
.013
T ULL >
Time OFF
ms
180000
100
180000
100
180000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.015
ULL < off
U
THR
OFF
%Unom
80
10
100
10
100
.016
ULL < on
U
THR
ON
%Unom
95
95
95
10
100
.017
T ULL <
Time OFF
ms
1500
1500
2400
0
60000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage1 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.019
ULN > off
U
THR
OFF
%Unom
110
100
130
100
135
U
THR
ON
Fixed Hysteresis (1% U
NOM
)
.021
T ULN >
Time OFF
ms
180000
100
180000
100
180000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Undervoltage1 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.023
ULN < off
U
THR
OFF
%Unom
80
10
100
10
100
.024
ULN < on
U
THR
ON
%Unom
95
95
95
10
100
.025
T ULN <
Time OFF
ms
1500
1500
2400
0
60000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Overvoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.027
ULL >> off
U
THR
OFF
%Unom
125
100
130
100
135
U
THR
ON
Fixed Hysteresis (1% U
NOM
)
.029
T ULL >>
Time OFF
ms
100
100
100
100
10000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.031
ULL << off
U
THR
OFF
%Unom
30
10
100
10
100
.032
ULL << on
U
THR
ON
%Unom
95
95
95
10
100
.033
T ULL <<
Time OFF
ms
800
800
800
50
60000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max