- Wire the detectors according to the wiring diagram. Make sure the load does not exceed 200 mA.

Symptom

Probable Reason

0666220608

Page 2 of 2

TELCO User Manual SG 10 Series

Corrective Action

Connect RX to master TX

Troubleshooting

2. Output indicator is flashing.

- Severe electrical interference

Change position of TX and RX

Remove RX and TX supply cable from high voltage cables

- RX cannot see TX

Remove obstruction

3.  Yellow LED on RX is constant off.

Check supply and cable to the master TX

1. Alarm indicator on RX is constant on.

- Master TX is disabled
- No syncronization signal

- Severe ambient light

Installation

 - It is recommended that the detectors are placed at least 5mm from edges for mechanical protection.

- Mount the detectors in correct position and correctly aligned according to Fig. 2 (Note *)

- Check for correct wiring before turning power on (Fig. 1).

- Make sure that the Output indicator (yellow LED) changes when beams are blocked.

* The master TX and master RX can run seperatly if required.

- When the Power on indicators (green LEDs) are on, the system is operating.

- If the Alarm indicator (red LED) is constant on the RX is not connected to master TX.

MASTER RX

MASTER TX

SLAVE TX

SLAVE RX

WALL

WALL

Fig. 2

TX

RX

Power on indicator

Output indicator 

Alarm indicator

Fig. 3