Service manual: TAC-12D-10 

5/9 

 

 

 

Fig. 4.2 D-SUB 9PIN female 

 

 

5.

 

Commencing operation and control behavior 

 

Following the completion of mounting and a waiting period of approximately 30 minutes 

(to allow oil to collect in the compressor in order to ensure lubrication and cooling) 

electrical connection can be made.   

 

The cooling unit operates automatically, i.e. after electrical connection, the internal fan 

will run continuously to circulate the air inside the enclosure. This results in a uniform 

temperature distribution in the cabinet. The compressor and heater (optional) are 

controlled by a microcontroller.   

 

● 

Compressor and external fan control 

If the temperature of internal air inlet exceeds P0 (35°C), the external fan and 

compressor will be switched on. 

Contrarily, if the temperature of internal air inlet is lower than P0-P1 (35-6=29°C), the 

external fan and compressor will be switched off. 

 

Important: 

In order to avoid cyclic operation, switch-on of compressor is delayed by 

about 3 minutes since last switch-off, please don’t take this as a failure! 

 

● 

Heater control (optional) 

If the temperature of internal air inlet is lower than P2 (5°C), the heater will be switched 

on. 

Contrarily, if the temperature of internal air inlet exceeds P2+P3 (5+10=15°C), the heater 

will be switched off. 

 

Содержание TAC-12D-10

Страница 1: ...Telca air conditioner unit TAC 12D 10 Service manual Document No TELCA0 010 0205 Edition No V1 0 TELCA SCIENCE TECHNOLOGY CO LTD...

Страница 2: ...t is thus largely maintenance free All that may be required from time to time is to clean the components of the external air circuit using a vacuum cleaner or compressed air if they become visibly dir...

Страница 3: ...aged packaging are an indication of refrigerant loss and leakage in the unit system Any damage to the packaging may be the cause of subsequent malfunctions After successful test and wire binding the w...

Страница 4: ...onditioner unit into front door of the cabinet position it on the fixing frame bonded with gaskets and rivet it with M4 nuts Care must be taken to ensure that the internal air outlet of the unit is co...

Страница 5: ...ed in the unit please notice the direction of the connector avoid put wrong and tighten the screws of the plug to secure the connection For detail connection details please view figure 4 1 and figure...

Страница 6: ...compressor and heater optional are controlled by a microcontroller Compressor and external fan control If the temperature of internal air inlet exceeds P0 35 C the external fan and compressor will be...

Страница 7: ...ooling cycle time when sensors defective P8 1 1 10 Machine address Keys introduction EXT Press the EXT button once to setting the parameter P2 press or button to modify the setting value press EXT but...

Страница 8: ...void cyclic operation switch on of compressor and external fan is delayed by about 3 minutes after the door has been closed Alarm output The air conditioner is permanently controlled by the microcontr...

Страница 9: ...g to the following trouble shooting chart Problem Potential Cause Solution No Power Check power source and electrical connections Fuse Blown on Control Board Replace with 3 15A slow blow fuse Unit not...

Страница 10: ...owever once the coils become visibly coated with dust it is recommended that they be cleaned with a brush or compressed air Both sides of the coils should be inspected regularly at least once every 12...

Отзывы: