Table 18 - Typical fault symptoms and methods of their elimination
Failure description
Possible reason
Method of elimination
Appearance failure
Mechanical or arc damage, breach of
service conditions
Replacement of failed component
Excessive contact resistance of ISM
ISM reached the permissible number of
operating cycles or decreasing of
insulation level in ISM vacuum
interrupters
Replacement of ISM
ISM cannot pass power frequency
voltage withstand test at 80 % of
rated voltage
ISM vacuum interrupters or insulation
damage
Replacement of ISM
ISM cannot perform close/trip
operation
ISM is interlocked
Check ISM interlock state and its
actuator coil connection with
connector X3 of CM
CM failure
Check CM LED states
Mechanical damage of ISM
Replacement of ISM
1 blink of CM “Malfunction“ LED
Absence of CM power supply
Check presence of CM power supply,
its polarity and voltage level
2 blinks of CM “Malfunction“ LED
ISM cannot be closed / tripped
Check the circuit of ISM actuator coil
connection with connector X3 of CM,
check state of ISM electrical interlocks
3 blinks of CM “Malfunction“ LED
ISM actuator coil circuit is interrupted
Check the circuit of ISM actuator coil
connection with connector X3 of CM,
check state of ISM electrical interlocks
4 blinks of CM “Malfunction“ LED
Short circuit of ISM actuator coil circuit
Check the circuit of ISM actuator coil
connection with connector X3 of CM,
check state of ISM electrical interlocks
5 blinks of CM “Malfunction“ LED
Manual trip of ISM and ISM is
electrically interlocked
Check the ISM and its interlock state
6 blinks of CM “Malfunction“ LED
Overheating of CM
Stop performing CO operations until
the blinks stop
7 blinks of CM “Malfunction“ LED
State of ISM is not defined
Check the ISM and its interlock state
CM “Malfunction“ LED lights
continuously
Internal fault of CM
Replacement of CM
None of CM LEDs lights
Absence of CM power supply
Check presence of CM power supply,
its polarity and voltage level
Internal fault of CM
Replacement of CM
The ISM or CM removal and the installation of the new one should be performed according to chapter 4. The
checks and tests after substitution are described in chapter 5.
Содержание TAVRIDA ELECTRIC VCB15 LD
Страница 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Страница 3: ...1 Product description...
Страница 7: ...2 Nameplates and seals...
Страница 11: ...3 Product handling...
Страница 23: ...4 Installation...
Страница 50: ...5 Commissioning...
Страница 57: ...6 Operation...
Страница 61: ...7 Maintenance and troubleshooting...
Страница 66: ...8 Disposal...
Страница 68: ...Appendix 1 Product range...
Страница 71: ...Appendix 2 Overall drawings...
Страница 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Страница 85: ...Appendix 3 Secondary schemes...
Страница 86: ...87...
Страница 87: ...88...
Страница 88: ...89...
Страница 89: ...90...
Страница 90: ...91...
Страница 91: ...92...
Страница 92: ...93...