Iris Packet Broker (IPB) 7.13.2
22
Hardware Installation and Maintenance Guide
3
IPB Installation
Rev. 001-140228
Connect IPB DC Power Supply 2 to Fuse Panel A Output Terminals and Ground
Connect IPB DC Power Supply 1 to Fuse Panel B Output Terminals and Ground
Connect the IPB DC grounding lugs to the fuse panel grounding lugs
Figure 3.2 - Component Power Cabling
Tektronix equipment, cables, and wiring diagrams comply with industry standard DC electrical color coding.
Please ensure proper cabling if your equipment and cabling uses nonstandard DC electrical color coding.
Improper cabling can cause damage to equipment or personal injury. Contact Tektronix to request specially
labeled power cables (-48V = Red, Return = Black) for the IPB.
Systems with multiple units require a grounding solution that can adequately ground all units.
shows an example grounding solution using a grounding bar. Note that
only shows grounding
cabling from the components to the grounding bar; refer to
for power cabling from the components
to the fuse panel.