05
step
GATEWAY ANALOG OUTPUTS
29
INSTALLATION GUIDE
PLUS TWP-XUT
04
Link
Analog Output Index 1
(Gateway) to
Temperature Input 1
(Transmitter) and configure MB Add Link according
to the previous step. Set minimum and maximum values and click on
Write
4000 (4mA)
20000 (20mA)
WIRELESS GATEWAY
Green led permanently on
during a closed current loop
Red led permanently on
during an open current loop
NOTE:
Output index 1 is linked to modbus address [9], according to mapping table of step 03.
Modbus address double word (float 32) value is converted into 4..20 mA scale according to minimum and
maximum defined values.