5  ASSIGNING TO THE SYSTEM 

 

1) 

Turn detector counterclockwise.  
 

2) 

Start assigning on the Security Hub mobile 
or desktop app. Assigning starts for 45-60 
sec. 
 

3) 

Insert battery into the detector: 

 

Secondary

 

– first 

Primary

 - next 

4) 

Detector’s led start flashing: 5x white flash 
in 1 sec. 

 
Make  sure  that  the  assigning  is  successful  on 
the  Security  Hub  mobile  or  desktop  app.  If  as-
signing is unsuccessful, repeat the procedure. 

 

6  RESET PROCEDURE 

1) 

Turn detector counterclockwise.

 

 

2) 

Close the DEL contacts - the red indicator 
will turn on. 

3) 

After turning off the red indicator, open the 
DEL contacts. 

4) 

The  detector  generates  a  notice “No  con-
nection”  and  becomes  available  for  as-
signing to the system. 

 
7  INSTALLATION  PLACE 

 

1) 

   Installation height should not exceed 10m; the 

minimum  distance  to  the  wall  -  0.1  m  must  be 
observed.

 

 

2) 

   Do not install the detector: 

in front of the air conditioner; 

in front of the window (dust can cause a 
false alarm of the detector). 

3) 

Do not mask the detector; smoke particles must 

freely enter the smoke chamber. 

 
ATTENTION!

  Remove  the  protective  cover 

immediately before commissioning the detector.

 

 

8  INSTALLATION  PROCEDURE  

 

1) 

Remove the elec-
tronic unit from the 
base

  

 

 

2)

 Mount the base on 

ceiling 

 

 

3) 

 Insert battery. 

 

Secondary

 

– first 

 

Primary

 - next 

 

4) 

 Install the electronic unit. 

5) 

 Perform detector test (see section 9).

 

 

9  TESTING 

Test  examines  the  electronic  circuit  of  the 
detector  and  the  smoke  chamber, 

except  for 

the  possibility  of  penetration  of  smoke  into 
the chamber.

  

The test is performed by the laser tester "Astra-
942" (not included). 

1) 

 To activate the 

«Test» 

mode: 

- press the 

red button

 of the laser tester;

 

direct laser beam to the detector’s LED; 

-  irradiate the LED for 

1 sec

LED should turn on in red for 2 sec. 

 

 

detector’s LED:

 

-

  normal  work:  1x  red  flash  in  every  2  sec. 

during 30 sec.  

-

  if there is a defect or malfunction: 3x red flash 

in 25 sec. period.

 

  Security  Hub

 

mobile  app

:  fire  alarm  notifi-

cation. 

 

10  WARRANTY 

 