2.2. Circuit outputs 

 
The central battery unit outputs can be con

nected by the “Mode” connectors (see page 6) in steps of 2 

circuits, either as maintained or non-maintained circuits.

 

 

2.3. Charging 
 

After a power failure or after installing the unit, the unit charges the batteries with constant current, until 
the battery voltage reaches the maintenance voltage level. The charging current can be selected from 
the charger module card with a DIP switch. See section 4.1. Setting the charging current. 
 

Network LED is lit, when the battery is charging 
Charging LED is blinking, when the battery voltage has not reached the maintenance voltage 
The charging LED is lit when the battery voltage has reached maintenance voltage.

 

 

2.4. Main voltage limits 
 

When the main voltage drops below 180 V, the unit changes to battery use. 

 
Battery use LED is lit

 

 
When the network returns or gets higher than 195 V, the unit changes again to mains use, and starts 
to charge the batteries. 
 

Main use LED is lit 
Charging LED is blinking or lit 

                

 

2.5. Battery voltage limits 
 

If the battery voltage rises over 260 V in normal mode, an over-voltage alarm is given.  

 

Main use LED is lit 
Over-voltage LED is lit 
Battery fault LED is lit 
Internal fault LED is lit 

                  

If the battery voltage drops under 228 V in normal mode, an under-voltage alarm is given.  

 

Main use LED is lit 
Under-voltage LED is lit 
Battery fault LED is lit

 

Internal fault LED is lit

 

 
When the unit is in battery mode, and the voltage drops below 195 V, a deep discharge alarm is given. 
 

Deep discharge LED is blinking 
Internal fault LED is lit

 

              

When the unit is in battery mode, and the battery voltage falls below 173 V, the unit goes into deep 
discharge protection mode, where the battery discharge is stopped. 

 

Battery use LED is lit

 

Deep discharge LED is lit 
Internal fault LED is lit

 

                  

 

Deep discharge LED stays lit until it is reset from the 

reset/test

 button. Resetting is possible only after 

the mains supply has returned. 
 
The unit can be switched to emergency mode also remotely, if this feature is used. 
 

Main use LED is blinking 
Battery use LED is lit 

 

Содержание TKT65 B Series

Страница 1: ...1 VOT6506E CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING Installation and maintenance instructions TKT65XXB P KEEP IN A SAFE PLACE FOR LATER USE...

Страница 2: ...Charging 5 2 4 Mains voltage limits 6 2 5 Battery voltage limits 6 2 6 Alarm relay outputs 6 2 7 Remote control 6 3 System installation 6 4 Implementation 6 4 1 Setting the charging current 7 5 Use 7...

Страница 3: ...rge limit 173 V The batteries 18 pcs for the unit always require a separate battery cabinet All the functions related to the use of the unit can be performed from the control panel that also includes...

Страница 4: ...t be suitable both for AC and DC supply 1 5 Directives and standards The following directives and standards were applied in designing and manufacturing the unit Quality ISO 9001 2000 certified quality...

Страница 5: ...charge the batteries Main use LED is lit Charging LED is blinking or lit 2 5 Battery voltage limits If the battery voltage rises over 260 V in normal mode an over voltage alarm is given Main use LED i...

Страница 6: ...and N After this connect the maintained and non maintained circuits to circuit boards TS10 TS13 CIRCUITS 1 6 The circuit fuses are located in fuse holders F1 F6 see Appendix 2 connections The outputs...

Страница 7: ...be set checked in the following way Set the current from the charging card TS5 DIP switch as indicated in the instructions NOTE The charging current must ALWAYS be set checked according to the number...

Страница 8: ...orded in the emergency lighting system maintenance manual which shall be shown to the authorities when requested 6 2 Replacing the batteries The batteries shall be changed in the following order take...

Страница 9: ...OVER VOLTAGE The battery voltage is higher than normal over 260 V BATTERY UNDER VOLTAGE The battery voltage is lower than normal under 228 V DEEP DISCHARGE The deep discharge protection of the battery...

Страница 10: ...10 APPENDIX 2 Connections...

Страница 11: ...11 APPENDIX 3 Part placement TS5 CHARGING CURRENT SETTING DIP SWITCH...

Страница 12: ...12 APPENDIX 4 Dimensions TKT65 B...

Страница 13: ...13 APPENDIX 4 Dimensions TKT65xxBP cabinet construction...

Отзывы: