background image

 

                                                                                                                                                      

 

                                                                                                                                                     1 

 

 

 

VOT6506E 

 

CENTRAL BATTERY UNIT FOR EMERGENCY 

LIGHTING 

 

Installation and maintenance instructions 

TKT65XXB(P) 

 

 

 
 
 
 
 
 
 

 

KEEP IN A SAFE PLACE FOR LATER USE 

 

Содержание TKT65 B Series

Страница 1: ...1 VOT6506E CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING Installation and maintenance instructions TKT65XXB P KEEP IN A SAFE PLACE FOR LATER USE...

Страница 2: ...Charging 5 2 4 Mains voltage limits 6 2 5 Battery voltage limits 6 2 6 Alarm relay outputs 6 2 7 Remote control 6 3 System installation 6 4 Implementation 6 4 1 Setting the charging current 7 5 Use 7...

Страница 3: ...rge limit 173 V The batteries 18 pcs for the unit always require a separate battery cabinet All the functions related to the use of the unit can be performed from the control panel that also includes...

Страница 4: ...t be suitable both for AC and DC supply 1 5 Directives and standards The following directives and standards were applied in designing and manufacturing the unit Quality ISO 9001 2000 certified quality...

Страница 5: ...charge the batteries Main use LED is lit Charging LED is blinking or lit 2 5 Battery voltage limits If the battery voltage rises over 260 V in normal mode an over voltage alarm is given Main use LED i...

Страница 6: ...and N After this connect the maintained and non maintained circuits to circuit boards TS10 TS13 CIRCUITS 1 6 The circuit fuses are located in fuse holders F1 F6 see Appendix 2 connections The outputs...

Страница 7: ...be set checked in the following way Set the current from the charging card TS5 DIP switch as indicated in the instructions NOTE The charging current must ALWAYS be set checked according to the number...

Страница 8: ...orded in the emergency lighting system maintenance manual which shall be shown to the authorities when requested 6 2 Replacing the batteries The batteries shall be changed in the following order take...

Страница 9: ...OVER VOLTAGE The battery voltage is higher than normal over 260 V BATTERY UNDER VOLTAGE The battery voltage is lower than normal under 228 V DEEP DISCHARGE The deep discharge protection of the battery...

Страница 10: ...10 APPENDIX 2 Connections...

Страница 11: ...11 APPENDIX 3 Part placement TS5 CHARGING CURRENT SETTING DIP SWITCH...

Страница 12: ...12 APPENDIX 4 Dimensions TKT65 B...

Страница 13: ...13 APPENDIX 4 Dimensions TKT65xxBP cabinet construction...

Отзывы: