TSD-5154 Optical Smoke and Heat Detector
With Relay, 24VDC
Installation Manual
Release Date: 26/11/2018
Rev:00
Important Warnings
General
✓
Read this manual carefully before operating the device and save it for later use.
✓
Follow all warnings and precautions mentioned in the user manual. Follow all operating
instructions, respectively.
✓
Keep the devices away from water and moisture.
Environmental Conditions
Do not operate the device in extreme hot and cold environments, except for the following conditions.
Temperature: -
10 ° C to +
55
° C
Relative Humidity: 95% RH max
Services
Do not try to repair the device yourself, if you open the cover of the device, you may be exposed to electric
shock.
In case of any malfunction, contact your dealer or authorized service. Technical intervention to the device
must be carried out by qualified service personnel.
Failure Conditions Requiring Service
In case of any malfunction or in the following cases, contact your authorized service or dealer.
✓
When the power cord or plug is damaged,
✓
When any liquid has flown into the device,
✓
When exposed to water or rain,
✓
If the device has been dropped or the casing has been damaged
✓
If the device has a noticeable level of performance change,
✓
If the device does not operate normally according to the operating instructions specified in the user
manual
Call the service as incorrect operations can cause other malfunctions..
What You Can Do Yourself
Do not try to repair the device yourself, as you may be exposed to electric shock if you open the cover of the
device. In case of any malfunction, contact your dealer or authorized service. Technical intervention to the
device must be carried out by qualified service personnel. The device should be cleaned with a dry cloth. No
chemicals should be used.
Transport and Shipping
The device should be handled with care so as not to experience any impact from outside and to prevent fluid
intake. Malfunctions during improper transport are out of warranty.
Human and Environmental Health
This device does not contain any chemical or biological substances that could harm human health.
General Features
✓
Advanced smoke detection algorithm that minimizes false alarms
✓
The detector works as A2S class and
it gives alarm at 55 °
C
✓
Rejection of temporary signals that can be detected as an alarm
✓
Adaptive protection by constantly sampling its environment
✓
The pollution algorithm and warning that understands that it is contaminated and unable to detect
✓
Easy to clean smoke chamber
✓
Two leds used for status indicators
✓
15s start time
✓
Suitable with TFA-0120 Universal Detector Base.
Technical Features
Power
18V(min)
–
24V(max)
Avarage Consumption
10mA (@24V)
Alarm Consumption
18mA (@24V)
Relay Out
NC 1A-10W
Humidity
95% RH (Max)
Dimensions (mm)
Ø110, h42
Body Material
White, UV Added ABS Plastic
Cable Select
0.4mm ² ~ 1.5mm ²
Weight (With/Without Base)
184 gr / 126 gr
Start Time
15 sec
Indication LEDs
Blue Led
RED Led
When the device is first energized,
and sampling the environment for
15s
Flashes in 5 sec period
X
Any Fault Condition
(Pollution or Power Fault)
Flashes in 1 sec period
X
Device is in normal operation
Flashes in 20 sec period
X
Alarm Condition
X
Permanent Lights
Terminals
Number 1
(-) Power
Number 2
Zone GND
Number 3
Zone Input
Number 4
(+) Power
Number 5
Ground
Warning: Do not attempt to take the card out of its plastic protection. It is sealed solely for
your safety. Users must avoid intervention
.