Tekmar Zone Control 367 Скачать руководство пользователя страница 13

13

Floating Action Zones

• If a floating action actuating motor is connected to the terminals 

Com 1-2 —1 —2 (19, 20 and 21), make sure power to the motor

circuit is off and install a jumper between the terminals 

Com 1-2 — 1 (19 and 20). When the circuit is powered up, the valve should

start to open. If it does not, check the wiring between the terminal and the actuating motor and refer to any installation or
troubleshooting information supplied with the motor. If the valve closes instead of opening, the wiring to the actuating motor must
be reversed. If the valve opens correctly, turn off the power to the circuit and remove the jumper. Install a jumper between the
terminals 

Com 1-2 — 2 (19 and 21). When the circuit is powered up, the valve should start to close. If it does not, check the wiring

between the terminal and the actuating motor and refer to any installation or troubleshooting information supplied with the motor.
If the valve closes correctly, turn off the power to the circuit and remove the jumper.

• If a floating action actuating motor is connected to the terminals 

Com 3-4 —3 — 4 (22, 23 and 24), follow a similar procedure

to that described above.

• If a floating action actuating motor is connected to the terminals 

Com 5-6 —5 —6 (25, 26 and 27), follow a similar procedure to

that described above.

Advanced Settings

Design Outdoor 

 

If the 

Design Outdoor dial is turned up from the Off position the Demand Limiting function

is enabled. The 

Design Outdoor dial determines the outdoor temperature at which full

heating output is required.

Floating Motor Speed

   

This dial is used to set the time required for the modulating valve to go from fully closed
to fully open.

Zone 2 Ventilating / Zone 2 Heating

 

 

  

If this DIP switch is set to 

Zone 2 Ventilating, the 367 can operate a ventilation system

through output relay 

2. If the DIP switches are set to Zone 1 Cooling and Zone 2

Ventilating, the 367 can operate a free cooling system through output relays 1 and 2. If
the DIP switch is set to 

Zone 2 Heating the 367 operates output relay 2 as a heating zone.

Testing the Control Functions

STEP SEVEN 

 OPERATIONAL TEST OF CONTROL FUNCTIONS  

The Zone Control 367 has a test routine which is used to test the main control functions. The 367 continually checks the sensors and
displays an error message whenever a fault is found. See page 15 for the list of error messages. When the 

Test button is pushed, the

Test light is turned on. The Heat Required, and Optimum Start / Stop lights are turned off and the individual outputs and relays are tested
in the following test sequence.

Test Sequence

   

Each step in the test sequence lasts 10 seconds. At the end of each step, the device continues to operate
until it is turned off in a later step.

During the test routine, the test sequence can be paused by pressing the 

Test button. The test sequence

remains paused at that point for up to 5 minutes. If the 

Test button is not pressed again while the test

sequence is paused, the control exits the entire test routine. Once the test sequence is paused, the 

Test

button can be pressed again to skip to the next step. This can also be used to rapidly skip through the test
sequence. To reach the desired step, repeatedly press and release the 

Test button until the appropriate

device and indicator light turn on.

Step 1  - The System Pump relay is turned on.

Step 2 - If the Com 5-6 common block is used for a single One Stage zone, the control

turns on relay 

5 for 10 seconds.

- If the 

Com 5-6 common block is used for two One Stage zones, the control turns

on relay 

5 for 10 seconds and then turns off relay 5 and turns on relay 6 for

10 seconds.

- If the 

Com 5-6 common block is used for a Two Stage zone, the control turns

on relay 

5 and then, after 10 seconds, turns on relay 6.

- If the 

Com 5-6 common block is used for a Floating zone, the control turns on

relay 

5  for 10 seconds and then turns off relay 5 and turns on relay 6 for

10 seconds.

- If an RTU is not connected to 

RTU 5 or RTU 6 , the control skips this step.

1

2

1

System Pump

5

Zone 5 / Lo stage /
Open

Zone 6 / Hi stage /
Close

6

4

Zone 4 / Hi stage /
Close

3

Zone 3 / Lo stage /
Open

2

Zone 2 / Hi stage /
Close / Ventilation

Zone 1 / Lo stage /
Open / Cooling

1

System Pump

Test

Zone 1 Cooling

Zone 2 Ventilating

Floating Motor

Speed

130 sec.

30

230

100

200

0

°

F

-40

Off

Design Outdoor

30

Содержание Zone Control 367

Страница 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Страница 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Страница 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Страница 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Страница 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Страница 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Страница 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Страница 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Страница 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Страница 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Страница 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Страница 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Страница 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Страница 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Страница 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Страница 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Отзывы: