Calls

CALLS

Displays any call for heat or cool the control 
is receiving. 

Pumps

PUMPS

Displays any pump currently operating.

Zones

1 2 3 4

ZONES

Displays if an on-board zone is operating.

Var

VARIABLE SPEED PUMP OUTPUT

Displays percent output of the variable speed 
pump.

WWSD / CWSD

The system is currently in Warm Weather Shut 
Down or Cold Weather Shut Down.

MIN / MAX

Heat pump is prevented from operating due 
to high or low return water temperature.

OCCUPIED

Indicates that a User Switch or Timer has put 
the system into Occupied. 

UNOCCUPIED

Indicates that a User Switch or Timer has put 
the system into UnOccupied. 

HEAT PUMP

Heat pump stage 1 or 2 is operating. 

Aux

AUXILIARY

An auxiliary backup heat source is currently 
operating using the Backup relay.

BOILER

Indicates that the boiler is operating (flashing 
flame indicates boiler is igniting). 

FLOOR

Radiant floor cooling is currently active.

BACKUP

Backup heat source is required to assist in 
heating the tank sensor to its target.

COOL / HEAT

The hea

t pump is operating in either cool or 

heat mode

°F°C   minhr

sec%

°F, °C, MINUTES, HOURS, SECONDS, %

Units of measurement for current number.

WARNING

Displays if an error exists on the system.

Symbols

Display

User Interface

Aux

Setpoint

Xfr

Var

Item Field

Displays the name 
of the selected item

Number Field

Displays the 
current value of 
the selected item

Status Fields

Displays the current status 
of the control’s inputs, 
outputs and operation. Most 
symbols in the status field 
are only visible when the 
VIEW Menu is selected

Menu Field

Displays the 

current menu

Navigating The Display

Menu Button

 -------------------------------------------------------------------------------------------

 -------------------------------------------------------------------------------------------

The 406 uses a simple user interface to accomplish a variety 
of functions. The four buttons beneath the display are used 

to change the menu, sort through Items, and adjust each 
setting as required.

The menus display in the Menu Field at the top left side of 
the LCD. Four menus are available: View, Adjust, Monitor and 
Toolbox (identified by the wrench symbol).

The View menu allows the user to view the current status 
of various system parameters.
The Adjust menu allows the installer to adjust settings to 

ensure control operation matches requirements of the me-
chanical system.
The Monitor menu keeps track of run times and other im-
portant data that is collected during system operation.
The Toolbox menu is a source of system information and 
includes useful tools for commissioning and testing the 
system.

Содержание tekmarNet 2 House Control 406

Страница 1: ...rts CSA C US Certified for use in USA and Canada Introduction The tN2 House Control 406 is designed to operate the equipment in a 2 pipe single tank hydronic heating and cooling system It operates two...

Страница 2: ...tended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Do not attempt to service the control Refer to qualifi...

Страница 3: ...llow proper wiring practices building and electrical codes for your jurisdiction Each cable must be pulled from the equipment to the electrical junction box It is recommended to label each cable for e...

Страница 4: ...ix System P DHW Pump Transfer Pum Variable Speed Pump Boil System Pump Figure 1 Connect Ground Wires Figure 2 Connect Neutral Wires for Power Source 1 Pull two conductor 18 AWG LVT cable up to 500 fee...

Страница 5: ...ly tucked inside the electrical box Using 2 of the 4 holes in the back of the enclosure securely fasten it to the junction box extension ring with 2 10 screws as shown in Figure 7 Install The Enclosur...

Страница 6: ...add additional Boil or Mix water temperature zones to the system install a tekmarNet Wiring Center Connect the Boil Mix terminals tN4 and C on the 406 to the corresponding tN4 and C Expansion termina...

Страница 7: ...heat pump Connect the Rc2 and Y2 terminals on the 406 to the R and Y2 terminals on the heat pump Connect the Rc1 and O B terminal on the 406 to the R and O or B terminal on the heat pump Wiring the A...

Страница 8: ...vided in the enclosure The other side of the terminal block is used to connect wires from the control A good quality test meter capable of measuring up to 5 000 k 1 k 1000 is required to measure the s...

Страница 9: ...peed setting Step 7 The mix system pump turns on for 10 seconds Step 8 The tank system pump turns on for 10 seconds Step 9 The O B contacts are closed for 10 seconds Step 10 The HP loop pump turns on...

Страница 10: ...easure between 103 5 V ac and 126 5 V ac Testing the Boiler Modulating Output This test applies for modulating boilers only Active the User Test sequence and pause at Step 18 by pressing the Item butt...

Страница 11: ...Menu An electric element in the system storage tank is switched on through an isolation relay with the backup relay on the 406 to provide backup heat to maintain the Tank Sensor S4 at its target temp...

Страница 12: ...Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call Mix DHW tN4 tN4 C C Mod dc mA Boil Mix Tank Rc2 Y2 Setpoint DHW...

Страница 13: ...nter 314 An electric boiler supplies backup heat using the Backup relay and the Transfer Pump P7 By setting HP LOOP to ON the HP Loop Pump P2 will operate whenever there is a call on the tank or mix b...

Страница 14: ...N 3 4 6 5 7 2 1 8 O C Y R O C Y R Transfer 314 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No...

Страница 15: ...pump starts adding heat to the storage tank use the backup delay setting in the adjust menu This ensures the heat pump is being used to its full potential before backup is allowed Placing the Transfer...

Страница 16: ...ack red black black black 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call M...

Страница 17: ...sed to its full potential before backup is allowed A non condensing boiler may be used since P1 provides boiler return protection preventing flue gas condensation Tank zones can have fan coils air han...

Страница 18: ...lack black black Variable Speed 314 T T Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power C...

Страница 19: ...or heating or mix the water temperature up above the dewpoint for floor cooling Expansion Tank Mechanical A406 5 S1 S2 S5 P3 tekmarNet 2 Thermostats tekmarNet 2 Thermostats P2 Z1 Z2 Z3 Z4 P5 Z9 Z10 Z1...

Страница 20: ...black black 3 4 6 5 7 2 1 8 314 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call...

Страница 21: ...CONDS Units of measurement for current number WARNING Displays if an error exists on the system Symbols Display User Interface Aux Setpoint Xfr Var Item Field Displays the name of the selected item Nu...

Страница 22: ...sing the up or down button This will permit setting changes to the control Programming and Settings The 406 settings can be found in the Adjust menu When changing the items value the setting is saved...

Страница 23: ...re the control is currently trying to maintain at the tank sensor The tank target is calculated based on the outdoor design and tank design settings is displayed when no heat is required for tank zone...

Страница 24: ...ith TANK links zones 1 4 to the tank loop BOIL links zones 1 4 to the boiler loop MIX links zones 1 4 to the mixing loop Note This item is only available when either mix or boil water temperatures hav...

Страница 25: ...SECTION D The outdoor air temperature used in the heating curves that determine the tank mix and boiler target temperatures Typically set to the temperature of the coldest day of the year 70 to 200 F...

Страница 26: ...g device does not provide boiler protection when Boiler Type is set to EMS1 or EMS2 10 to 230 seconds Default 30 seconds Access Installer Set to BOILER MOTOR SPEED SECTION G Time in seconds from full...

Страница 27: ...HOVER SECTION E O Close O B contacts to operate heat pump in cool mode B Close O B contacts to operate heat pump in heat mode 2 to 20 F 1 to 11 C Default 4 F Access Installer Set to HEAT PUMP DIFFEREN...

Страница 28: ...CTION E Minimum compressor off time for the heat pump 10 to 180 minutes OVR Default 60 minutes Access Installer Set to BACKUP DELAY SECTION E The time that heat pump s have to run at full output befor...

Страница 29: ...only available when HP TYPE 2STG or ROT 0 to 9999 Hours Default 0 hr Access User RUN TIME BOILER The total on time of the backup relay since the item was last reset Press and hold the Up and Down butt...

Страница 30: ...Hours Default 0 hr Access Installer RUN TIME MIX SYSTEM PUMP The total running time of the Mix System Pump since this item was last reset Press and hold the Up and Down buttons while viewing to reset...

Страница 31: ...ble items When set to USER all thermostats are locked and the number of thermostat settings available are reduced OFF SEL Default Off Access Installer FACTORY DEFAULTS Loads the factory default settin...

Страница 32: ...ATERTEMP setting in the Adjust Menu to configure the proper water temperatures for the application The following table references application drawings with different water temperatures selected Applic...

Страница 33: ...so used to give a boiler enable to allow the modulating boiler to go through the ignition sequence The Backup relay may not be required on all modulating boilers EMS1 The Mod dc mA output uses 0 10 V...

Страница 34: ...ots of glass and high solar gains by extracting heat away from the slab before it is able to heat the room Floor is displayed in the Mode status field while doing floor cooling Enable Floor Cooling Fo...

Страница 35: ...utdoor design These two parameters set the upper point for each heating curve Adjust the BOIL DSGN MIX DSGN and TANK DSGN settings in the Adjust Menu Boiler and Tank Minimum The BOIL MIN and TANK MIN...

Страница 36: ...naturally recover better since there are longer periods of time between the heat pump transferring heat to or from the ground source GEO Source Staging Longer times between cycles Stage 2 ON Y2 Stage...

Страница 37: ...ontrol shuts down the heat pump when the outdoor temperature falls below an adjustable temperature to prevent energy waste from unnecessary heat pump operation during cooling Use the Y COOLING CWSD se...

Страница 38: ...Adjust Menu to adjust the preheat tank target The heat pump will target a water temperature 20 F 11 C higher than the preheat tank target at the return sensor The heat pump target is limited by the H...

Страница 39: ...here are four items that determine the boiler target temperature 1 2 Differential 1 2 Differential Boiler Target Boiler On Boiler Off Boiler Differential Both on off and modulating boilers are operate...

Страница 40: ...ings for House Control 406 with Common Modulating Boilers Modulating Boiler Operation The 406 can operate a single hot water modulating boiler using the Mod dc mA output and the Backup contact Not all...

Страница 41: ...setting Note Setpoint operation has no priority Boiler System Pump Setpoint Pump Setpoint ON ON or OFF Zone Pump ON or OFF Setpoint Operation The control can operate to satisfy the requirements of a...

Страница 42: ...g set to On The control is not in Warm Weather Shut Down Xfr The House Control 406 operates six different pump outputs on the back side of the enclosure The Pumps box in the status field indicates whi...

Страница 43: ...supply sensor As a result the control operates the variable speed pump at a fixed output as long as there is a Mix Call Locate and repair the problem as described in the Test the Sensor Wiring sectio...

Страница 44: ...me once the sensor problem is corrected The error message self clears once the error condition is corrected DOMESTIC HOT WATER CALL ERROR A DHW sensor and a DHW call have been applied at the same time...

Страница 45: ...cking for the flashing Warning symbol Once the error on the device is corrected the error message will clear DEVICE ERROR AT ADDRESS M 01 to M 24 Each tekmarNet device thermostat setpoint control time...

Страница 46: ...tem in AWAY During AWAY the thermostats operate at a lower temperature Locate a User Switch and set to Normal to resume heating MODE setting The mode of the 406 can be set to Auto Cool Heat Backup or...

Страница 47: ...TANK DSGN TANK MIN MIX DSGN BOIL DSGN BOIL MIN BOIL MOTR MIN MOD MOD DELAY WWSD OCC WWSD UNOCC INTERLOCK COOL SETP Item Setting DEW POINT COOL MIN SWITCHOVER HP DIFF HP2 DELAY HP LOOP HP RETURN MAX H...

Страница 48: ...sponsibility and obligation Pur chaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to a...

Отзывы: