background image

© 

2010     D 

156 

06/10 

of 

12 

The control is mounted in accordance with the instructions 
in the Data Brochure D 001.

Step Two — Mounting

Step Three — Rough-in Wiring

The wiring terminates in the two wiring chambers on the 
control. Determine whether the low voltage wiring enters 
the wiring chamber through the back or the bottom of the 
control. The wiring is roughed-in prior to installation of the 
control (see Brochure D 001). Standard 18 AWG solid wire 
is recommended for all low voltage wiring, and multi-strand 
16 AWG wire is recommended for 120 V (ac) wiring.

Power must not be applied to any of the wires during 
the rough-in wiring stage.

Install the Source Sensor 085 and Storage Sensor 071 
according to the instructions in the Data Brochures D 085 
and D 070, and run the wiring back to the control.
Run wires from the 24 V (ac or dc) power to the control. 
Use a clean power source to ensure proper operation.

Step Four — Testing the Wiring

The following tests are to be performed using standard 
testing practices and procedures, and should only be 
carried out by properly trained and experienced persons.

A good quality electrical test meter, capable of reading from 
at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is 
essential to properly test the wiring and sensors.

Test the Sensors

In order to test the sensors, the actual temperature at 
each sensor location must be measured. A good quality 
digital thermometer with a surface temperature probe is 
recommended for ease of use and accuracy. Where a 
digital thermometer is not available, a spare sensor can be 
strapped alongside the one to be tested, and the readings 
compared. Test the sensors according to the instructions 
in the Data Brochures D 085 and D 070.

Test the Power Supply

Make sure exposed wires and bare terminals are not in 
contact with other wires or grounded surfaces. 

If a 24 V (ac) transformer is used, make sure the voltmeter 
is set to AC. Turn on the power and measure the voltage 
across the 24 V (ac) power supply. The reading should be 
between 22 and 26 V (ac).

Class 2

Transformer

L

N

R

C

If a DC power source is used, make sure the voltmeter 
is set to DC. Turn on the power and measure the voltage 
across the 24 V (dc) power supply. The reading should be 
between 20 and 28 V (dc). 

24 V (dc)

Battery

+

-

Test the Outputs

Relay (terminals 3 & 4)

Make sure the power to the pump circuit is off and install 
a jumper between terminals 3 & 4. When the pump circuit 
is powered up, the pump should turn on. If the pump fails 
to operate check the wiring between the terminals and 
the pump and refer to any installation or troubleshooting 
information supplied with the pump. If the pump operates 
correctly, disconnect the power and remove the jumper.

Pump

L

N

3

4

Relay

Содержание Difference Setpoint Control 156

Страница 1: ...a heat source Additional functions include 24 V ac OR 24 V dc power supply Monitor Minimum Maximum temperatures for Source Storage Displays number of running hours of the relay Displays T hours to per...

Страница 2: ...e 156 has three push buttons Item for selecting viewing and adjusting settings When programming the control record settings in the PRGM menu table which is found in the second half of this brochure It...

Страница 3: ...that follows will explain the on and off points of the relay T Source Maximum Minimum Storage T hours Diff l Item Number Field Displays the current value of the selected item Item Field Displays the c...

Страница 4: ...low the Minimum Source Setpoint the relay is turned off The relay remains off until the source temperature rises above the Minimum Source Setpoint plus the Minimum Source Differential The Source Minim...

Страница 5: ...429 50 29 34 C 446 60 70 F 57 C 411 60 55 48 C 425 Table 1 K values at 120 F 49 C for different heat transfer solutions based on glycol K increases with temperature Improper installation and operation...

Страница 6: ...and sensors Test the Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperature probe is recomme...

Страница 7: ...he control These terminals are to be used as a switch to either make or break the pump circuit When the 156 requires the pump to run it closes the contact between terminals 3 and 4 Sensors and Un powe...

Страница 8: ...s Diff l 76 to 284 F 60 to 140 C STORAGE TEMPERATURE Current storage temperature as measured by the storage sensor HEAT is displayed if the relay is closed T Source Maximum Minimum Storage T hours Dif...

Страница 9: ...down buttons for 1 second T Source Maximum Minimum Storage T hours Diff l 0 to 999 999 hr RELAY RUNNING HOURS Number of Relay running hours since this item was last cleared The control will display t...

Страница 10: ...Default 40 F 4 C SOURCE MINIMUM SETPOINT If the Source temperature drops below this setpoint the relay is turned off T Source Maximum Minimum Storage T hours Diff l 2 to 45 F 1 to 25 C Default 10 F 6...

Страница 11: ...f l EEPROM READ ERROR The control was unable to read a piece of information from its EEPROM This error can be caused by a noisy power source The control will load the factory defaults and stop operati...

Страница 12: ...ether direct indirect special secondary incidental or consequential arising from ownership or use of the product or from defects in work manship or materials including any liability for fundamental br...

Отзывы: