Technical Data

tekmarNet

®

4 Thermostat 538; 

One Stage Heat

Packaged weight

0.8 lb. (380 g)

Enclosure

White PVC plastic, NEMA Type 1

Dimensions

2-7/8” H x 2-7/8” W x 13/16” D (73 x 73 x 21 mm)

Approvals

CSA C US, meets Class B: ICES and FCC Part 15

Ambient conditions

Indoor use only, 32 to 122°F (0 to 50°C).

RH max 92% to 104°F (40°C), and 50% above 104°F 
(40°C)

Altitude <9840 feet (3000 m), Installation Category II, 
Pollution Degree 2

Power supply

24 V (ac) ± 10% 50/60 Hz, 1.8 VA Standby, 56 VA fully 
loaded, NEC / CEC Class 2

W Relay

24 V (ac) 2 A

Sensors:

NTC thermistor, 10 kΩ @ 77°F (25°C ± 0.2°C) ß = 3892

– Optional

tekmar type # 070, 072, 073, 076, 077, 079, 084

Job Record

Jobsite Location  ________________________________________________

Thermostat Location _____________________________________________

Item

Setting

Item

Setting

Set Room Heat 

Set Floor Min 

Set Room Heat 

Set Floor Max

Set Room Heat Away

Schedule Member

Set Floor Heat 

Heat Supply Pump

Set Floor Heat 

Heat Supply Pump Delay

Backlight

Heat Cycles Per Hour

Units

Air Group

Max Set Room Heat 

Room Sensor

Max Set Room Heat 

Sensor

Min Set Room Heat

tekmarNet

®

 Address

Set Floor Min 

Floor Cooling

Содержание D538

Страница 1: ...zation Zone Post Purge Intelligent setback Timer 033 Scenes Away override Auto Heating Cycle tekmarNet 4 communication compatible Requires 4 wires Pulse Width Modulation CSA C US Approved for use in U...

Страница 2: ...ng the Thermostat Wiring 4 Mounting the Thermostat 5 Cleaning the Thermostat 6 Switch Settings 6 User Interface 7 Display 7 Button Operation 7 Symbols Description 7 Settings 8 14 Sequence of Operation...

Страница 3: ...ire is 500 feet 150 m Strip wire to 3 8 10 mm for all terminal connections Use standard 4 conductor 18 AWG wire Installation Location Removing The Thermostat Base Push tab 1 Remove thermostat from bas...

Страница 4: ...anager Connect the optional auxiliary sensor wires to the sensor terminals 5 and 6 1 2 3 4 tN4 Wiring Center or tN4 Zone Manager Slab Sensor 072 073 079 OR Outdoor Sensor 070 OR Indoor Sensor 076 077...

Страница 5: ...should appear on the display 6 There should be continuity between the R 3 and W 4 terminals Testing the tekmarNet 4 Bus The symbol is shown on the display when communication is present If the thermost...

Страница 6: ...back schedule as a schedule member if available Requires the installation of a Timer 033 to use this feature OFF OFF The thermostat does not follow a programmable setback schedule 2 ON SCENE The therm...

Страница 7: ...GROUP The air group is cooling Heating can start once the cooling is finished LOCK Locked to User access level CLOCK Operating on a programmable schedule tekmarNet Communication is present WARNING SYM...

Страница 8: ...ler SET ROOM HEAT AWAY Set the room heating temperature while in the Away scene Continued on next page Press and hold down both the and buttons for 2 seconds to change from one step to the next Releas...

Страница 9: ...ng in the Adjust menu is set to Off 40 to 122 F 4 5 to 50 0 C Default 65 F 18 5 C Installer User SET FLOOR HEAT Set the floor heating temperature while in the event Available when A slab sensor is ins...

Страница 10: ...rge number with Software Version upper right corner and the thermostat address 40 to 95 F 4 5 to 35 0 C Default 85 F 29 5 C Installer MAXIMUM SET ROOM HEAT Set the maximum room heating limit while in...

Страница 11: ...n AND A slab sensor is installed on the auxiliary sensor input AND Sensor setting in the Adjust menu is set to Floor Off 40 to 122 F Off 4 5 to 50 0 C Default Off Installer User SET FLOOR MINIMUM Set...

Страница 12: ...liary sensor input AND Sensor setting in the Adjust menu is set to Floor 1 2 3 4 Default 1 Installer SCHEDULE Thermostat can follow schedule master 1 2 3 or 4 Available when Switch setting 1 is set to...

Страница 13: ...e tekmarNet system Choose Synchronize when zone heated using a boiler Choose Auto when zone is non hydronic heating Available when No reset control on the tekmarNet system ADJUST ADJUST OFF 1 to 16 In...

Страница 14: ...t control mixing Installer tekmarNet ADDRESS The address is shown in the large number field Auto is shown in the upper number field when using automatic addressing Press the or the button to manually...

Страница 15: ...the thermostat is heating The heat can cycle on and off within 1 5 F 1 C of the Set Room Heat temperature Freeze Protection The thermostat operates the heat whenever the room or floor temperature fall...

Страница 16: ...r the group This thermostat can be set to be a member of the air group When operating as an air group the air temperature readings of all the air group member thermostats are communicated to the air g...

Страница 17: ...e Display Room Temperature Setting 1 or or Follows programmable schedule or operates at the occupied temperature 2 Away Away temperature 3 Unoccupied temperature Scenes System Override Section E When...

Страница 18: ...d BUS ERROR The tekmarNet 4 communication bus has either an open or a short circuit The result is that there are no communications Check for loose wires Check for short circuits between the tN4 and C...

Страница 19: ...hort circuit error This error cannot be field repaired Contact your wholesaler or tekmar sales representative for details on repair procedures ROOM SENSOR OPEN CIRCUIT The built in air temperature sen...

Страница 20: ...nsor was intentionally removed locate the Room Sensor setting in the Adjust menu and set to On Power the thermostat down and up to clear the error OUTDOOR SENSOR SHORT CIRCUIT The auxiliary outdoor se...

Страница 21: ...clears after the auxiliary room sensor fault is corrected AUXILIARY ROOM SENSOR OPEN CIRCUIT The auxiliary room sensor has an open circuit Check for loose or damaged wires Locate and repair the proble...

Страница 22: ...arly so that the room is comfortable at the scheduled time Pressing button does not increase temperature Flashing Max Installer can increase the Maximum Set Room Heat Flashing Floor Max Floor temperat...

Страница 23: ...z 1 8 VA Standby 56 VA fully loaded NEC CEC Class 2 W Relay 24 V ac 2 A Sensors NTC thermistor 10 k 77 F 25 C 0 2 C 3892 Optional tekmar type 070 072 073 076 077 079 084 Job Record Jobsite Location __...

Страница 24: ...s not cover the cost of the parts or labor to remove or transport the defec tive Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s ag...

Отзывы: