Outdoor
Current outdoor air temperature as measured by the outdoor
sensor. This item is only available when the
External Input
/
Stand
Alone DIP switch
is set to Stand Alone.
-76 to 149°F
(-60 to 65°C)
Boiler Supply
Current boiler supply water temperature as measured
by the boiler supply sensor.
-22 to 266°F
(-30 to 130°C)
Boiler Target
Boiler target temperature is the temperature the con-
trol is currently trying to maintain at the boiler supply sensor.
– – –, 35 to 230°F
(– – –, 2 to 110°C)
Boiler Return
Current boiler return water temperature as measured
by the boiler return sensor.
A boiler return sensor must be installed to view this item.
-22 to 266°F
(-30 to 130°C)
Boiler
Δ
T
The actual temperature difference between the boiler
supply and the boiler return sensors.
A boiler return sensor must be installed to view this item.
0 to 252°F
(0 to 140°C)
Boiler 1 Modulation
Current percent modulation of the boiler’s
burner. This item is only available when Boiler 1 is set to Au
(automatic).
0 to 100%
Boiler 2 Modulation
Current percent modulation of the boiler’s
burner. This item is only available when Boiler 2 is set to Au
(automatic) or CP1 (copy 1).
0 to 100%
Boiler 3 Modulation
Current percent modulation of the boiler’s burner.
This item is only available when Boiler 3 is set to Au (Automatic) or
CP1 (copy 1) and DHW MODE is set to OFF.
0 to 100%
A
Boiler 1 Hours
The total running time of boiler 1 since this item
was last cleared. To clear this item, press the
▲
and
▼
button
simultaneously while viewing this item.
This item is only available when Boiler 1 is set to Au (automatic).
0 to 1999 hr
A
Boiler 2 Hours
The total running time of boiler 2 since this item
was last cleared. To clear this item, press the
▲
and
▼
button
simultaneously while viewing this item.
This item is only available when Boiler 2 is set to Au (automatic) or CP1.
0 to 1999 hr
A
Boiler 3 Hours
The total running time of boiler 3 since this item
was last cleared. To clear this item, press the
▲
and
▼
button
simultaneously while viewing this item.
This item is only available when Boiler 3 is set to Au (automatic) or
CP1 and DHW MODE is set to OFF.
0 to 1999 hr
Display
Description
Range
Section
Installer
Ad
v
View
Menu (1 of 1)