© 2005
D 545 - 06/05
16 of 40
Item Field
Range
Access
Description
NONE, ZONE,
MST1, MST2,
MST3, MST4,
MBR1, MBR2,
MBR3, MBR4
Default = NONE
USER
INST
ADV
HEAT SCHEDULE
SECTION
L
If a schedule is not required, select NONE.
If the schedule is only used by this thermostat, select
ZONE.
If the schedule is shared with other thermostats,
select MST1 to MST4.
If the schedule is set on another thermostat, select
MBR1 to MBR4.
Note:
This item is only available when the COOL SCH
is set to either NONE or MBR1 to MBR4. This item
can be viewed in the USER and INST access levels
but can only be adjusted in the ADV access level.
NONE, ZONE,
MST1, MST2,
MST3, MST4,
MBR1, MBR2,
MBR3, MBR4
Default = NONE
USER
INST
ADV
COOL SCHEDULE
SECTION
L
If a schedule is not required, select NONE.
If the schedule is only used by this thermostat, select
ZONE.
If the schedule is shared with other thermostats,
select MST1 to MST4.
If the schedule is set on another thermostat, select
MBR1 to MBR4.
Note:
This item is only available when the HEAT SCH
is set to either NONE or MBR1 to MBR4. This item
can be viewed in the USER and INST access levels
but can only be adjusted in the ADV access level.
24 hr, 5-2,
5-11, 7dAY
Default = 5-11
USER
INST
ADV
SCHEDULE TYPE
SECTION
L
Select the type of schedule.
Note:
This item is only available when the Heat or
Cool Schedule are set to ZONE or MST1 to MST4.
2 (Occ, UnOcc),
4 (Wake, UnOcc,
Occ, Sleep)
Default = 4
USER
INST
ADV
SCHEDULE MODE
SECTION
L
Select the number of events per day.
Note:
This item is only available when the Heat or Cool
Schedules are set to ZONE or MST1 to MST4.
Schedule Menu (1 of 4)
The Schedule menu items set the schedule type, the
number of events per day, and the event times.
Continued on next page.
SCHEDULE MENU