Stand 30.10.2019
32
ENG
LIS
CH
14.3
Adjusting the heat output
A default heat output is set for every air curtain. Please only change it if you notice that the
temperature of the discharged air is too low. You would waste energy with a thermostat that is set
too high.
For electrically heated systems, you can control the heat output in 3 steps on the controller.
For all other systems you can control the heat output on the control valve thermostat.
If you no longer need the changed setting, reset it to the manufacturer’s default.
14.4
Adjusting the air discharge nozzle
You can turn the air discharge element easily by hand
up to 16 degrees towards the in- or outside. So that
you obtain maximum insulation, the air discharge
element must be turned appropriately towards the
outside.
14.5
How to install your air curtain system on the floor
You should first determine where the device is to be installed. The position should ensure that neither
the air intake area nor air discharge nozzle is blocked. Now place the base plate where the system is to
be installed; it will initially be used as a template.
Mark the positions for drilling holes in the floor, remove the base plate, and drill the holes. Then fix
the base plate to the air curtain system using the screws provided. Now you can fix the base plate and
the air curtain system to the floor using heavy duty dowels. This completes the installation on the
floor. The electrical and heating-connections must now be laid.
You can choose to lay the connections from the top or from the side.
It is essential to use all specified anchor points on the air curtain system! Special TEDDINGTON
mounting materials can be obtained from Teddington. The mounting materials must be adapted to
the local situation, and the structural stability checked where necessary. The supplied mounting
parts must be checked for suitability and replaced if necessary. The specialist installation company
has sole responsibility for safe installation.