              POWER SUPPLY 

 

 

      The VRT600 control unit must be supplied with 85-250Vac 50/60Hz.  

       A variation in the network voltage of over 10% might cause alarms because of the current variation in the load. 

 

If the electrical system is affected by harmonic frequencies, alarm warnings might be triggered because of the 
consequent variation in the current absorbed by the motors. 

 

It is good practice to make sure that the level of system harmonics is not such as to cause malfunction or damages to 
all  the  connected  electrical  and  electronic  instruments,  in  compliance  with  the  regulations  in  force  for  the  type  of 
system.  
 
When the control unit is powered directly by the secondary of the transformer to be protected, it can be burnt out by 
high intensity overvoltages. 
These problems occur if the main switch is closed and the transformer does not have the load (no load test). 
The above is much more evident when the 220 Vac voltage is taken directly from the bars of the secondary of the 
transformer and there is a fixed capacitor battery for power factor correction of the transformer itself. 

 
 

              OPERATION

 

 

When switched on, the device carries out a LAMP TEST and is set either in REMOTE or LOCAL mode, according to how 
it was set before being switched off. 

 

In REMOTE mode the fans are activated when contact 60-61 closes, which must be connected to the FAN contact of 
the temperature control unit. 

 

In LOCAL mode the fans are activated by pressing the <START-STOP> button. The status of operation is stored in 
case of power failure. 

 
 

HOW TO CHECK THE ALARM STATUS

 

 

 

Running LED OFF: 

no ventilation activation control 

 

Running LED ON: 

REMOTE or LOCAL ventilation activation 

 

Over- and under-current LEDs OFF: 

motor operating correctly 

 

Over-current LED ON: 

motor stopped due to over-current 

 

Under-current LED ON: 

motor w under-current alarm signal 

 

Under-current LED flashing: 

motor disconnected while auto-tuning 

 

Over-current LED ON: 

motor consumption >5.5A (immediate trip without any delay) 

 

All LEDs flashing: 

corrupted memory error (ech); press reset and repeat the programming procedure 

 

 

   N.B.: 

A motor in a state of alarm or the interruption of supply to the device make contacts 8-9 of the FAULT relay  

   

close. 

 
 

              HOW TO RESET A MOTOR IN ALARM

 

 

To reset an alarm due to under-current or over-current, press the RESET button after carrying out the necessary 
checks and any repairs might be required. 

 

 
             OPERATION WITH FANS NOT TECSYSTEM 

  

           The proper functioning of the VRT unit is guaranteed only for: fans with current absorption between 250mA (IN MAX 
           20%) or 300mA (IN MAX 30%) and 5A, single phase, single speed and power variation is not greater than ± 10%. 
                   

 

 
 
                             IMPORTANT NOTE: if an existing control unit must be replaced with a new one, to guarantee its  
             correct and safe operation, all the connecting terminals must be replaced with the new terminals supplied,  
             on  condition  the  brand  of  the  new  terminals  is  different  from  the  one  of  the  previously  installed  ones

Содержание VRT600 ED18

Страница 1: ...es with ISO9001 certified quality system http www tecsystem it R 1 9 26 11 20 ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT600 INSTRUCTION MANUAL Translations of the original instructions ...

Страница 2: ...antage of all its functions ATTENTION THIS MANUAL IS VALID AND COMPLETE FOR THE UNIT VRT600 ED18 PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 MOUNTING 8 6 ELECTRICAL CONNECTIONS 9 VRT600 BACK POWER SUPPLY 10 OPERATION HOW TO CHECK THE ALARM STATUS 7 PROGRAMMING 11 8 WARRANTY CONDITIONS 12 9 TROUBLESHOOTING 10 EQUIPMENT DISPOSAL 11 USEFUL CONTACTS 13 C...

Страница 3: ...et or humid hands If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents and compressed air OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect the control unit and contact an enginee...

Страница 4: ...371 Screws tightening torque 0 5Nm 1 supply terminal 3 poles pitch 5 Code 2PL0367 Screws tightening torque 0 5Nm 2 Motor line terminals 6 poles pitch 5 Code 2PL0372 Screws tightening torque 0 5Nm 1MN0030 REV 2 ATTENTION always install the device using the terminals included in the pack The use of terminals other than those included with the control unit might cause malfunctions ACCESSORIES ...

Страница 5: ...ections on removable terminal strips OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COSФ 1 contacts 6 outputs M1 M2 M3 M4 M5 M6 5A max 85 250Vac 50 60Hz DIMENSIONS 100x100 mm din43700 depth 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from electrical interference EN 61000 4...

Страница 6: ...t film polycarbonate IP65 DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent overcurrent LED s running remote local LED s prg setting cal Initial AUTO TUNING to set up motors operation Front button to START STOP motors locally Front alarm RESET button Access to programming through front button IMPORTANT WARNING Before carrying out the isolation test of the electrical panel the control unit is in...

Страница 7: ...ation LED yellow 4 LED yellow warning motors M1 M2 M3 M4 M5 M6 are in under current 13 Fans local management LED yellow 5 Fixing block 14 Fans remote control LED green 6 Fans local START STOP button 15 Programming selection LED yellow In d start d trip 7 Fans control mode REM LOC button REMOTE or LOCAL 16 Monitoring delay LED yellow at start up d start 8 ENT RESET button alarm reset and programmin...

Страница 8: ... 2 1 3 1MN0063 REV 2 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING ...

Страница 9: ...60Hz 6 Remote enabling contact ENABLE 3 Control unit supply 85 250 Vac 50 60 Hz 7 5 VA 7 FAULT relay fault signal 4 M1 M2 M3 fan line supply 85 250Vac 15 Amp max 50 60Hz Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER NO FAUL ELECTRICAL CONNECTIONS 6 7 1 2 3 4 5 1MN0050 REV 3 ...

Страница 10: ...of the temperature control unit In LOCAL mode the fans are activated by pressing the START STOP button The status of operation is stored in case of power failure HOW TO CHECK THE ALARM STATUS Running LED OFF no ventilation activation control Running LED ON REMOTE or LOCAL ventilation activation Over and under current LEDs OFF motor operating correctly Over current LED ON motor stopped due to over ...

Страница 11: ... start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seconds the CAL LED flashes and LEDs 0 5 10 20 30 light up in sequence When the calibration is completed the control unit resets and goes into REMOTE mode N B any connection or programming errors might cause fan malf...

Страница 12: ...rogram the device M1 M2 M3 M4 M5 M6 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming procedure All the LEDs are ON Likely microcontroller fault return the device to Tecsystem for repair Contact TECSYSTEM Technical Department if the problem persists European direc...

Страница 13: ...VRT600 USEFUL CONTACTS TECHNICAL INFORMATION ufficiotecnico tecsystem it SALES INFORMATION info tecsystem it 13 ...

Отзывы: