T2612 UNI 

TECSYSTEM  S.r.l ® 

11) COOLING-FAN CONTROL 

 
The T2612 unit, if suitably programmed, can control the ON/OFF of the transformer fans 
according to the set temperature values.  
The fans of the machine can be controlled in two different ways: 
 

• 

using the temperatures surveyed by the sensors on the three columns 

 

CHF

 1 2 3 - CH4 excluded 

    

ALARM

 and 

TRIP 

LED 1.2.3 illuminated (e.g. F1: ON at 80°C - OFF at 70°C) 

                                                                  (e.g. F2: ON at 90°C - OFF at 79°C) 

 

• 

by an additional sensor (

CH4-YES

) for the ambient temperature inside the transformer 

box. 

CHF 4 
ALARM 

TRIP

  LED Ch4 illuminated (e.g. F1: ON at 40°C - OFF at 30°C) 

                                                              (e.g. F2: ON at 45°C - OFF at 35°C) 

Press

 

 

and

 

 

key to select this function.

 

 
It is possible to operate the fans manually by pushing the 

AUTO/ON 

key. 

 

12) FAN TEST 
 

It is possible, through programming (

HFn

), to lay down that fans are activated for 5 minutes 

each “

xxx

” hours, regardless of column or room temperature values (ex.: with HFn=001 fans 

are  activated for 5 minutes each hour; 

Maximum value: 240).

 

This function has the aim to periodically verify the working of the fans and their control ap-
paratus during long idle periods. 
Loading 

000

 value, this function is inhibited. 

 
13) HOLD FUNCTION 
 

To select the hold function choose the program option 

HLD-Yes

. With hold function en-

abled, when temperature exceeds the alarm set point value, the alarm relays will energize 
and the alarm LED’s will illuminate until you reset the relay contacts in manual reset mode. 
Reset is only possible when temperature falls below the set point value. To exclude the hold 
function select the program option 

HLD-no

 
14) DISPLAY MODE 
 

By pressing 

DISPLAY MODE 

you can select one of the three display modes: 

 

• 

HOT    

: the display shows automatically the temperature of the hottest channel

 

• 

MAN   

: each channel may be viewed manually by pressing the 

 or 

 key.

 

• 

T.MAX

: the unit shows the max. temperature recorded by the sensors and any alarm 

        

 

 

recorded   after the last reset. To check the channels press 

 or 

 key.

 

• 

SCAN 

:  channels cyclically change every 2 seconds

 

Содержание T2612

Страница 1: ...http www tecsystem it T2612 T2612 B T2612 C T2612 AD INSTRUCTION MANUAL TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 T2612 UNI TECSYSTEM S r l R 1 3 07 09 12...

Страница 2: ...upply to sensors Accuracy 1 full scale 1 digit Ambient operating temperature 20 C to 60 C Humidity 90 non condensing Housing painted steel panel frontal part in polycarbonate IP65 Burden 7VA Data stor...

Страница 3: ...ays can be used for fan control or else they can be included in the conditioning circuit of the transformer box 5 THERMOMETRIC SENSORS CONNECTION Each Pt100 sensor has three conductors one white and t...

Страница 4: ...it normal operation if the Fcd YES function has been selected the display will show Fcd indicating that a sensor is damaged and the LED corresponding to the affected channel will lighten The FAULT rel...

Страница 5: ...es ex with HFn 001 fans are activated for 5 minutes each hour Maximum value 240 This function has the aim to periodically verify the working of the fans and their control ap paratus during long idle p...

Страница 6: ...n 2 2nd cooling relay Alr alarm relay trP trip relay Use the Scroll or keys to make the selection Press the SET key to perform the test on the selected relay To reset press the RESET key and will appe...

Страница 7: ...abled function 21 PRG SET Fcd appears on display 22 Enter Fcd YES or NO Fcd YES control of damaged Pt100 connected 23 PRG SET Hld appears on display HLd YES HOLD feature enabled 24 Enter HLd YES or NO...

Страница 8: ...by the General Conditions of Sale Tecsystem srl RAEE This SYMBOL shown on the unit indicates that the waste must be subject to separate collection The end user must send the unit to the waste collect...

Страница 9: ...r When switching the unit on off the alarm and trip relays energize Strong electrical noise is being picked up on the power line Check to ensure the shield of the sensor cable is connected to the pane...

Страница 10: ...cable to be used to guarantee a correct working of the network is con cerned we suggest to follow what is provided for by EIA RS485 standard which advises the use of a 24AWG loop In order not to affec...

Страница 11: ...1 Function code not present 2 Wrong data address 3 Wrong data i e length WRITING DATA CODE 16 10 Writing questions Slave addr 16 10 Starting address Hi Starting address Lo Number of registers Hi Numbe...

Страница 12: ...ck Y n 00 19 00 Alarm memory bit 7 6 5 4 3 2 1 0 CH4 CH3 CH2 CH1 CH4 CH3 CH2 CH1 TRIP ALARM 31 CRC CALCULATION This protocol includes 2 byte CRC 16 in all the transmission The typical polynomial 11000...

Страница 13: ...ALVANIZED SHEET IRON Thickness 1 2 mm FRONT VIEW Cut out 155 X 280 mm Screw rivet M3 x 15mm Screw rivet M3 x 15mm Screw rivet M3 x 15mm 190 mm 210 mm 150 mm 150 mm 320 mm Screw rivet M3 x 15mm Screw r...

Страница 14: ...14 T2612 UNI TECSYSTEM S r l T2612 REAR CONNECTIONS CH4 CH3 CH2 CH1...

Страница 15: ...15 T2612 UNI TECSYSTEM S r l T2612 FRONT PANEL...

Страница 16: ...16 T2612 UNI TECSYSTEM S r l NOTES...

Отзывы: