SAFETY REQUIREMENTS 

                 
    ATTENTION:  

  
  

Carefully read the manual before starting using the control unit. Keep the instructions for future reference. 

 

  
 
                
 

Do not open the device, touching any internal component can result in electric shock as voltages over 50 volts 

can be lethal. In order to reduce the risk of electric shock, do  not disassemble the back of the device. Warranty shall be 
void if device is opened.    
  

Before connecting the device to the power supply, ensure that all the connections are correct. 

Always disconnect 

the unit from the supply before making any modification on the wiring. 
 
  
                Any operation on the equipment must be operated by a qualified technician. 
  

Failure to comply with these instructions can cause damages, fires or electric shock, and possible serious injuries! 

 

POWER SUPPLY

 

The NT935 WS can be supplied from 85 to 260 Vac-Vdc, irrespectively of polarity in Vdc. Before use, ensure that the power 
cable is not damaged, knotted or pinched. Do not tamper with the power cable. Never disconnect the unit by pulling the 
cable, avoid touching the clamps. Do not carry out any connecting/disconnecting operation with wet hands. To disconnect 
the device, do not use objects such as levers. Immediately disconnect the device if you smell burning or see any smoke: 
contact technical service. 

  

LIQUIDS   

 

Do not expose the equipment to liquid spurts or drops, do not position it in places where humidity exceeds 90% and never 
touch it with wet or humid hands. If any liquid penetrates the control unit, disconnect immediately and contact technical 
service.   

  

CLEANING

 

Disconnect  the  power  cable  before  cleaning  the  control  unit,  using  a  dry  cloth  without  any  solvent  or  detergent,  and 
compressed air. 

  

OBJECTS

 

Never insert objects into the openings of the control unit. If this happens, disconnect the control unit and contact technical 
service.  

  

USE RESERVED TO QUALIFIED PERSONNEL

 

The purchased good is an advanced electronic device that should not be used by non-qualified personnel. Any operation 
must be carried out by a qualified technician.  

  

ACCESSORIES

 

The  use  of  non-original  accessories  or  spare  parts  may  damage  the  unit  and  endanger  users'  safety.  In  event  of  fault, 
contact technical service. 

  

LOCATION 

Install the control unit indoor, in a place protected from water splashes and sun rays. Do not place near heat sources if 
exceeding the parameters stated in this manual. Position on a stable surface, far from any possible vibrations. Position the 
unit as far as possible from intense magnetic fields. 

  

REPAIRS

 

Do not open the control unit. In case of fault, always contact qualified personnel. The opening of the control unit and/or the 
removal of the series identifying label automatically make the warranty void. The warranty seal is applied to all devices, 
any attempt to open the unit would cause the seal to break the consequent automatic cancellation of the warranty. 

  

FUNCTION  
To control the transformer correctly from a temperature point of view, enabling the VOTING function is allowed 
where the load distributed between the phases of the transformer is adequately balanced.   

 

TECHNICAL INFORMATION 

  

Mail: [email protected] 

— tel: 02/4581861  

 

Содержание NT935 WS

Страница 1: ...ith the ISO9001 certified quality system http www tecsystem it R 1 3 26 11 20 Translations of the original instructions INSTRUCTION MANUAL NT935 WS TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fa...

Страница 2: ...35 WS PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL...

Страница 3: ...2 TECSYSTEM WEB SERVER 21 WEB SERVER MANAGEMENT BAR 22 HOME SCREEN SETTINGS SCREEN 23 NETWORK SETTINGS 24 OPTIONS 25 GRAPHICS SCREEN 26 EVENTS SCREEN 27 GRAPHIC VIEW NOTES 28 EXPORT NOTES CSV FILE PIN...

Страница 4: ...netrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth without any solvent or detergent a...

Страница 5: ...orque 0 5Nm 1 relay terminal 12 poles pitch 5 Code 2PL0361 Screw tightening torque 0 5Nm 1 Pt100 sensors terminal 12 poles pitch 3 81 Code 2PL0420 Screws tightening torque 0 25Nm 1 external Wi Fi SMA...

Страница 6: ...s FAN 1 and FAN 2 SPST Output relays with 10A 250Vca res COS 1 contacts Wi Fi Connection protocol 802 11 b g n frequency 2 4 GHz with removable external antenna Max 100m in open field DIMENSIONS 100 x...

Страница 7: ...l 4 2 ON OFF thresholds for FAN 1 and FAN 2 Sensor diagnostics Fcc Foc Fcd Data memory diagnostics Ech Access to programming through front keyboard Automatic exit from programming display and and test...

Страница 8: ...LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode selecti...

Страница 9: ...und in the measurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repairs 4 Pt Err This message appears when it is detected that one or more P...

Страница 10: ...ly after suitably fixing the device 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing blocks 4 Cross head screwdriver 1X100mm MOUNTI...

Страница 11: ...point key 2 Power supply 85 260Vac dc 50 60Hz 5 Antenna and Wi Fi connector 3 Relays FAN2 FAN1 ALARM TRIP FAULT 1MN0095 REV 0 Output relay with 10A 250Vac res COS 1 contacts COS 1 STOP SYSTEM ALARM C...

Страница 12: ...FAULT contact programmed in failsafe mode default YES opens 11 12 when the equipment is supplied only if the unit detects no fault on switching on and stays in this condition until one of the followi...

Страница 13: ...INT If INT is selected read function notes page 17 8 CH4 is displayed CH4 enabling 9 Select YES or NO with YES CH4 is enabled with NO CH4 is disabled 10 The ALARM threshold for CH4 is displayed the Al...

Страница 14: ...ect YES or NO Default YES 36 END is displayed End of programming 37 Press ENT to save the set data and exit programming Err incorrect programming of the LED values note 6 38 Return to step 1 PROGRAMMI...

Страница 15: ...mm 4 The cable screening must be grounded only with a termination preferably on the unit side 5 The sensors signal transfer cable must not be near electrical cables either low or medium high voltage 6...

Страница 16: ...emperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switching of the TRIP disconnect contact only if the TRIP threshold has been exceeded on at least two channels over the...

Страница 17: ...ration and their control apparatus periodically By setting NO this function is inhibited To enable the HFN function read the programming section on pages 13 14 INTELLIFAN FUNCTION What it is used for...

Страница 18: ...imits are reached preset temperature or for device s power supply lack FAULT Setting YES Fail safe the contact 11 12 is positioned as normally open switches closed when a fault condition is identified...

Страница 19: ...signal transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur leadin...

Страница 20: ...l network key TECSYSTEM in the network key window repeat the operation in the network key confirmation window Click on CONNECT Once the connection is established your device will indicate Connected TE...

Страница 21: ...ice will follow a chronological order but will not have the date time data available Accessing the Options page it will be possible to set the date time data manually see page 24 NOTE in the Access po...

Страница 22: ...or fault indications activation of the F1 F2 ALARM TRIP alarms WEB SERVER MANAGEMENT BAR The web manager management bar allows the user to identify the cabin and to select the various screens The foll...

Страница 23: ...g of the NT935 WS control unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 As for the panel programming also for programming through WEB SERVER it is necessary to follow these rules AL ALARM TRIP FAN FAN OFF...

Страница 24: ...erification 4 Subnet mask 7 Server NTP address automatic time and date update 1 Selection ACCESS POINT mode settings 8 Access Point SSID default TECSYSTEM network name modification 9 Password default...

Страница 25: ...IN CODE settings and operation at page 28 Selection Duration in days months Selection Duration in days months 5 min 91 days 3 months 20 min 365 days 12 months 10 min 182 days 6 months 30 min 547 days...

Страница 26: ...5 View key 3 Data availability DA yy mm dd Time hh mm ss 6 Export key VIEW button Pressing the VIEW button will update the chart according to the dates selected FROM TO FROM box It allows the user to...

Страница 27: ...time clock set to last saved Reset date and time automatic from the last saving W02 Real time clock manually set Manual date and time setting W03 diagnostic button pressed the access point key has be...

Страница 28: ...nce universal coordinated time Following the exporting of the CSV file recorded TEMPERATURE VALUE the last 300 recorded points will be contained in the file if there are less than 300 points in memory...

Страница 29: ...s wrong Contact the TECSYSTEM Technical Department Sudden trip of the main switch The temperature is on standard levels Just one channel has caused the trip Check the temperatures recorded in T MAX ch...

Страница 30: ...CONTACTS The product NT935 4 WS has born as a technical evolution of the NT935 WS model it maintains the main features of the NT935 WS increasing its programming flexibility 1 The 4 channels CH1 CH2 C...

Страница 31: ...MASS OF THE EQUIPMENT 0 45 Kg INPUT SUPPLY 100 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay output 10A 250Vac res COS 1 PORT Wifi Suitable for...

Отзывы: