background image

NT538 ETH

 

 

 

 

 

 

 
 
 
 
 
 
 

 

 

 

  

PAGE 

1)   SAFETY REQUIREMENTS 

………....................................... 

2)   ACCESSORIES 

………………………………….. 

3)   TECHNICAL SPECIFICATIONS 

………………………………….. 

4)   FRONT PANEL  

………………………………….. 

 

DISPLAY 

………………………………….. 

 

OPERATING PROGRAM CONTROL 

 …………………………………. 

— 

 

NOTES ON SCAN AND MAN FUNCTIONS 

………………………………….. 

— 

 

LED TEST 

………………………………….. 

— 

 

ALARM RELAY TEST  

………………………………….. 

— 

 

ALARM RELAY SILENCING  

………………………………….. 

— 

5)   MOUNTING      

………………………………….. 

10 

6)   ELECTRICAL CONNECTIONS  

………………………………….. 

11 

 

NT538 ETH BACK  

………………………………….. 

— 

 

POWER SUPPLY  

………………………………….. 

12 

 

ALARMS AND VENTILATION  

………………………………….. 

— 

 

FAULT AND RESET MESSAGE SEQUENCE 

………………………………….. 

— 

7)  PROGRAMMING 

………………………………….. 

13 

 

NT538 ETH 

………………………………….. 

— 

 

PROGRAMMING NOTES 

………………………………….. 

14 

 

TEMPERATURE SENSORS 

………………………………….. 

15 

 

MEASUREMENT SIGNAL TRANSFER  

………………………………….. 

— 

 

TEMPERATURE SENSOR DIAGNOSTICS  

………………………………….. 

16 

 

VOTING FUNCTION 

………………………………….. 

— 

 

PROGRAMMED DATA DIAGNOSTICS 

………………………………….. 

17 

 

TEMPERATURE DIAGNOSTICS 

………………………………….. 

— 

 

COOLING FAN CONTROL 

………………………………….. 

— 

 

FAN TEST 

………………………………….. 

— 

 
 
 
 

 

 

CONTENTS

 

 

INTRODUCTION 

First of all we  wish to thank you for choosing to use a 

TECSYSTEM

 product and recommend you read this instruction 

manual  carefully:  You  will  understand  the  use  of  the  equipment  and  therefore  be  able  to  take  advantage  of  all  its 
functions. 

  

ATTENTION! THIS MANUAL IS VALID AND COMPLETE FOR THE NT538 ETH CONTROL UNIT 

 

Содержание NT538 ETH

Страница 1: ...with ISO9001 certified quality system http www tecsystem it R 1 7 01 08 19 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT538 ETH INST...

Страница 2: ...ING 13 NT538 ETH PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS 17 TEMPERATURE DIAGNOSTICS COOLIN...

Страница 3: ...OTE PROGRAMMING 19 ERROR CODES ILLEGAL DATA 20 MODBUS MAPPING TABLE 9 ETHERNET MODULE PARAMETER PROGRAMMING 26 ETH0 CONNECTIONS TELNET ENABLING TELNET SCREEN 27 IP PARAMETER PROGRAMMING MENU 28 10 FAI...

Страница 4: ...enetrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth without any solvent or detergent...

Страница 5: ...ws tightening torque 0 5Nm 1 relay terminal 12 poles pitch 5 Code 2PL0361 Screws tightening torque 0 5Nm 2 Pt100 sensor terminal 12 poles pitch 3 81 Code 2PL0430 Screws tightening torque 0 25Nm ACCESS...

Страница 6: ...FAULT relay SPST Output relays with 10A 250Vac res COS 1 contacts 2 ventilation management relays SPST FAN 1 AND FAN 2 Ethernet output 10Base T 100Base TX Modbus TCP slave DIMENSIONS 100x100 mm din437...

Страница 7: ...rom 0 C to 240 C 1 alarm thresholds for each channels 1 Trip thresholds for each channels 2 ON OFF thresholds for FAN 1 and FAN 2 in common for all enabled channels Sensor diagnostics Fcc Foc Fcd Data...

Страница 8: ...LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode selecti...

Страница 9: ...turn the control unit to TECSYSTEM for repairs 3 CAL Err This message appears when damage is found in the measurement circuit The temperature values displayed might be incorrect Return the control uni...

Страница 10: ...lied 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing block 4 Cross head screwdriver 1X100mm MOUNTING 1 1MN0007 REV 0 2 3 1 2 3 4 1M...

Страница 11: ...signal transfer paragraph on page 15 Note relay contact image in non alarm condition with the exception of the FAULT relay that switches contacts 11 12 open NO contacts 11 12 closed NC fault conditio...

Страница 12: ...not monitor the temperature and the relays are all blocked The fault contact switches and the fault LED flashes Vis programming display PRG Programming Relay test The ALARM and TRIP relays switch onl...

Страница 13: ...D flashes Default 119 C 8 Set the desired threshold 9 it is displayed the CH1 FAN activation FAN1 and FAN2 ARE flashing info functioning fans fan control section page 17 10 Select YES FAN1 FAN2 enable...

Страница 14: ...ting programming without saving the modified data 3 After 1 minute s keyboard inactivity programming is abandoned without saving the data 4 During programming the control unit does not control protect...

Страница 15: ...e not complied with 1 The electrical field propagating from the power line of another circuit couples capacitively with the conductors in particular with unscreened cables The effect of this coupling...

Страница 16: ...the VOTING works Taking advantage of the principle indicated we use the probes installed to monitor the operation of the electrical machine but at the same time ensure the proper functioning of the p...

Страница 17: ...te FAN dedicated to that channel YES FAN1 FAN2 enabled flashing The selected channel CHn enable the switching of both contacts FAN1 and FAN2 in relation to thresholds ON OFF programmed for FAN1 and FA...

Страница 18: ...those in the paragraph regarding the remote programming notes The ETH module is always in slave mode The NT538 ETH control unit is in communication with the network only when it is in temperature read...

Страница 19: ...mand Write is carried out a check of compatibility data If you have a non compatibility exception for an answer and the data packet is rejected in its entirety The code of the first erroneous data can...

Страница 20: ...s reading the register 7 NO ERROR CH_1 Trip Alarm CH_2 Trip Alarm CH_3 Trip Alarm CH_4 Trip Alarm CH_5 Trip Alarm CH_6 Trip Alarm CH_7 Trip Alarm CH_8 Trip Alarm FAN_1 ON OFF FAN_2 ON OFF No channels...

Страница 21: ...R 16 00 FREE See Note 17 00 Address Modbus address 1 255 R 18 00 Bdr Modbus baud rate 0 2400 1 4800 2 9600 3 19200 4 38400 R 19 00 Parity Modbus parity bit 0 N 1 1 stop 1 Even 2 Odd 3 N 2 2 stop R 20...

Страница 22: ...temperat 0 C 240 C 0 C 200 C R 35 2 compl sign 2 compl Ch3 temper alarm set point 1 C 240 C 1 C 200 C As AL RW 36 2 compl sign 2 compl Ch3 temper trip set point 1 C 240 C 1 C 200 C As TRP RW 37 2 com...

Страница 23: ...t point 1 C 240 C 1 C 200 C As TRP RW 49 2 compl sign 2 compl Ch7 temper 10 C 240 C 48 C 200 C R 50 2 compl sign 2 compl Ch7 max temperat 0 C 240 C 0 C 200 C R 51 2 compl sign 2 compl Ch7 temper alarm...

Страница 24: ...tatus See Note CHx R 71 Ch7 story Ch7 status See Note CHx R 72 Ch8 story Ch8 status See Note CHx R INFO various causes READ BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 RESET R has taken place COMM...

Страница 25: ...us BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 FAULT Relay 1 ON TRIP Relay 1 ON ALARM Relay 1 ON FAN_2 Relay 1 ON FAN_1 Relay 1 ON CPU ERROR BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 PT ERRO...

Страница 26: ...net program to set the Ethernet IP parameters 1 START menu Windows If already enabled the program appears 2 Start the search with the Telnet program Press ENTER to launch the program Entering telnet i...

Страница 27: ...restart the PC if required 9 START menu Windows 10 Search for the Telnet program 15 Enter 192 168 10 120 9999 16 Press ENTER 12 TELNET SCREEN 11 Press ENTER to launch the program 13 Enter OPEN 14 Pre...

Страница 28: ...e modified by the operator 2 Communication parameters between the ETH0 port and the control unit 3 Communication configuration between the ETH0 port and the control unit 4 Communication advanced setti...

Страница 29: ...p 2 Enter the desired new Gateway IP address press ENTER if you wish to keep the set address press ENTER 4 times At the end of the operation the system will ask if you wish to modify Netmask Enter Y t...

Страница 30: ...ts are in positions 5 7 Alarm and 8 10 Trip they switch only when limits are reached preset temperature or for device s power supply lack FAULT Setting YES Fail safe the contact 11 12 is positioned as...

Страница 31: ...f the installation instructions are not complied with see page 15 any interference on the Pt100 sensor line can cause false readings or anomalous alarms Setting the FCD function in a temperature range...

Страница 32: ...roblem persists European directive 2012 19 EU WEEE has been approved to reduce electrical and electronic waste and promote the recycling and reuse of the materials and components of said equipment cut...

Страница 33: ...main circuit 18AWG working temperature over 105 C MASS OF THE EQUIPMENT 0 45 Kg INPUT SUPPLY 100 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay...