Basic manual for CP-1004 module
13
TXV 110 04
bances. It might be required in such cases that the user takes necessary measures to avoid
this.
** Fc test according to
Č
SN EN 60068-2-6 (idt IEC 68-2-6:1995), 10 cycles in each axe.
1.3 SYSTEM PARAMETERS
Real time circuit (RTC)
yes
Memory of user program and tables
192 + 64 KB
EEPROM program backup memory
yes
DataBox - additional data memory
512 kB
Internal memory for project archiving
2 MB
RAM and RTC backing up *
typ. 500 hours
Cycle time for 1k of log. instructions
0,2 ms
Number of user registers
65536
- remanent registers (from the number of
user registers)
16384
Total number of Tecomat timers and counters
32768 (16 bit
ů
)
Tecomat timers range
65 536 × 10 ms ÷ 10 s with possibility of cascading
Tecomat counters range
65 536 with possibility of cascading (16 bits),
4 294 967 296 (32 bits)
Supporting of IEC timers / counters
yes
Binary inputs and outputs
typ. 130
Instruction length
2 ÷ 10 bytes
CPU series
K
Number of serial channels **
2
Ethernet interface 10/100 Mb
1
CIB (Common Installation Bus)
1
TCL2 bus
1
* Valid for the central unit without supply, when the supply is on, the battery is disconnected.
** CH1 serial interface is fitted with fixed RS-232 interface. CH2 serial interface is optional by
means of exchangeable sub-modules.
1.4 ELECTRICAL PARAMETERS
Digital input circuits parameters
Number of inputs *
8*
Number of inputs in a group
8
Galvanic isolation of internal circuits
Ne
Diagnostics
signalizace vybuzeného vstupu na pane-
lu modulu
Common pole for the group
mínus
Input type
typ 1
Input voltage
for log. 0 (UL)
max. +5 V DC
min. –5 V DC
for log. 1 (UH)
min. +15 V DC
typ. +24 V DC
max. +30 V DC
Input current at log. 1
typ. 5 mA