14
TS1061 Dual Wiegand Interface Installation Manual
Figure 6: Two-state monitored input circuits
The panel uses the circuit’s resistance to determine the state of the input. In this
example, 10 kΩ EOL resistors have been used:
• 10 kΩ indicates sealed
• Open circuit or short circuit indicates unsealed
To use two-state monitoring, tamper monitoring must be disabled for the
Challenger
Plus
panel or Network Access Controller. See the
ChallengerPlus
Programming Manual
or the
TS1066 Network Access Controller Programming
Manual
, respectively, for information on disabling tamper monitoring.
Note:
Two-state monitoring is not compatible with input types 33 or 40. See the
ChallengerPlus Programming Manual
for details.
Wiegand reader connections
The TS1061 Dual Wiegand Interface can have two Wiegand devices, such as
readers, connected to terminal blocks shown on Figure 2 on page 8, item 12.
Figure 7 on page 15 details typical Wiegand reader wiring.