TECNOWARE declines any responsibility if this warning is disregarded. 

Warning  to  the  technical  personnel  authorized  for  service:  since  internal  components 
are  connected  to  the  batteries,  they  will  remain  powered,  and  therefore  dangerous, 
even  after  the  UPS  has  been  disconnected  from  AC  power  mains.  Before  any  repair or 
maintenance work, disconnect the batteries, by removing the positive cable (red colour) 
from the positive pole of the battery.  

 
 

ANOMALY 

POSSIBLE CAUSE 

ACTION TO SOLVE 

The UPS does not 
turn on 

ON/OFF button 

Press the ON/OFF button and check that is pushed. 

Batteries are flat 

Recharge the batteries for at least 4 hours. 

Electronic board failure 

Refer to Technical Service. 

The UPS always 
function on 
Battery mode 

Input mains power cable 
is disconnected. 

Check the input mains power cable. 

Check the presence of the electrical mains. 

Input mains fuse is burnt  Replace the fuse with another of the same type. 

Black-out conditions / 
surge/ Over-Voltage or 
Low-Voltage 

Wait until the AC Input Line returns to normal conditions. 

Electronic board failure 

Refer to Technical Service. 

Battery Autonomy 
is too short 

Battery is not fully 
charged. 

Recharge the battery for at least 6 hours. 

Electronic board failure 

Refer to Technical Service. 

“OVERLOAD” alarm  “OVERLOAD” condition 

Disconnect all devices that cause the overload condition. 

“FAULT” alarm 

“FAULT” condition 

Check if UPS is in OVERLOAD condition. 

Refer to Technical Service. 

The UPS does not 
communicate with 
the Computer  

The UPS Management 
Software sends a 
communication error 

Check that the USB (or RS232) cable is correctly connected 
between the UPS and the Computer.  

The Software is not 
correctly installed 

Install correctly the specific Software for your Computer’s 
Operative System. 

 

If the described anomalies should continue despite the advised troubleshooting, or should they 

manifest in any other form, please contact: 

TECNOWARE SERVICE 

www.tecnoware.com

 

Содержание ERA PLUS 1.100

Страница 1: ...Uninterruptible Power Supply ERA PLUS 900 ERA PLUS 1 100 User s manual...

Страница 2: ......

Страница 3: ...9 9 Maintenance 11 9 1 UPS Cleaning 11 9 2 Battery 11 9 3 Battery Replacement 11 9 4 Operator Safety 12 10 Troubleshooting 12 Conformity to the European Directives 14 Product Disposal 14 Lead Batteri...

Страница 4: ...he batteries they will remain powered and therefore dangerous even after the UPS has been disconnected from AC power mains Before any repair or maintenance work disconnect the batteries by removing th...

Страница 5: ...ure or a low battery condition directly to a computer this makes it possible to automatically save your data during an extended black out with the most widespread operating systems Windows Mac OS X Li...

Страница 6: ...ackaging and carry out a meticulous inspection We recommend keeping the original packaging in a secure place in case you need to send the UPS for maintenance purposes In case of transport damage notif...

Страница 7: ...d measurements Front panel shown below consists of two parts 1 The ON OFF button enables the user to turn ON OFF the UPS 2 The LINE BATTERY led this led blue color is always on during the functioning...

Страница 8: ...50 V 3 Grounded UPS Output receptacles Schuko Italian type black colour to supply critical loads 4 Computer Interface USB connector it is the communication USB port Only for UPS ERA Plus 1 100 In case...

Страница 9: ...g correctly 7 Simulate a black out by removing the AC Input line The UPS starts working in Battery mode the UPS emits a brief acoustic signal every 10 seconds 8 Be sure that all the devices connected...

Страница 10: ...seconds and simultaneously the LINE BATTERY led flashes 6 3 Low Battery and Automatic Restart In Battery mode ERA PLUS indicates the Low Battery condition whenever the battery reaches a charge level...

Страница 11: ...chapter Technical Characteristics as this may damage the unit In this case the warranty is void 6 5 Fault Condition The UPS indicates the Fault condition by emitting a continuous acoustic alarm During...

Страница 12: ...ve CEI EN 62040 2 2006 EMC Directive Battery Type Lead acid sealed free maintenance Number of batteries 1 Nominal Battery Voltage 12 Vdc Battery Specifications 12 Vdc 4 5 Ah 6 cells 12 Vdc 7 2 Ah 6 ce...

Страница 13: ...Take in mind that batteries are recharged automatically if the UPS works in Normal mode or if the UPS is off and connected to the AC Input Line Battery life strongly depends on the ambient temperatur...

Страница 14: ...afety Whenever the UPS is not responding anymore to original characteristics the UPS must be made non operative and every usage not authorised must be avoided After it will be necessary to refer to qu...

Страница 15: ...cal mains Input mains fuse is burnt Replace the fuse with another of the same type Black out conditions surge Over Voltage or Low Voltage Wait until the AC Input Line returns to normal conditions Elec...

Страница 16: ...rban waste but must be treated as a separate waste Any violation is indictable with financial sanctions as per in force regulations An incorrect waste disposal or an improper use of the same or of any...

Страница 17: ......

Страница 18: ......

Страница 19: ...TECNOWARE s r l www tecnoware com...

Отзывы: